beautypg.com

Det-Tronics EQP Fire and Gas Detection/Releasing System SAFETY MANUAL User Manual

Page 15

background image

5.1

95-8599

13

Table 1 provides the low demand EQP SIL 2 Safety

Function model and recommendations for complex

modeling (see Note 3).

PFDavg for each element is calculated according

to the equation above, where

l

DU

is the undetected

dangerous failure rate per 10

9

hours and T1 is the proof

test interval. (In this example, T1 is chosen as 1 year

(8760 hours) for all components of the safety function).

The value of PFDavg for the system is the sum of

PFDavg for the individual elements.

Note

the eQP system is an energize to trip system.
the power supply to the output device should
be monitored and annunciated when lost. this is
counted as a Dangerous Detected (DD) fault. If the
power supply is not monitored, it must be counted
as a Dangerous Undetected (DU) fault.

Example 1 (figure 3A)
Fire input from an X3301 and output to an EDIO.

PfDavg

= 0.58 x 10

-3

+ (0.38 x 10

-3

+ 0.1 x 10

-3

) +

0.1 x 10

-3

+ valve & supply = 1.16 x 10

-3

+ valve & supply

Example 2 (figure 3B)
Gas alarm from a PIRECL and output to an EDIO.

PfDavg

= 0.58 x 10

-3

+ (0.38 x 10

-3

+ 0.1 x 10

-3

) +

0.1 x 10

-3

+ valve & supply = 1.16 x 10

-3

+ valve & supply

Example 3 (figure 3C)
Input from an EDIO and output to the same EDIO.

PfDavg

= 0.003 x 10

-3

+ (0.38 x 10

-3

+ 0.1 x 10

-3

) +

0.1 x 10

-3

+ valve & supply = 0.58 x 10

-3

+ valve & supply

Using the table given in the standard, this value would

be suitable for a low demand SIL 2 safety function.

Other conditions (hardware fault tolerance and safe

failure fraction) also allow its use in a SIL 2 application.

See IEC 61508-6 for a more comprehensive guide to the

calculation of PFDavg.

Safety function

INPUT

Safety function

OUTPUT

Sff

Total failure

Rate

DU

(failure to Trip)

SU

(false Trip)

DD

(Detected fault)

X3301 FIRE InPUT

EDIO OUTPUT

(OPEn MOnITORInG) 96.6%

7,070 FIT

242 FIT

226 FIT

2,980 FIT

EDIO FIRE InPUT

(OPEn & SHORT

MOnITORInG)

EDIO OUTPUT

(OPEn MOnITORInG) 96.9%

3,580 FIT

110 FIT

130 FIT

2,020 FIT

PIRECL GAS InPUT

EDIO OUTPUT

(OPEn MOnITORInG) 96.2%

6,420 FIT

242 FIT

316 FIT

3,920 FIT

EDIO GAS InPUT

(OPEn & SHORT

MOnITORInG)

EDIO OUTPUT

(OPEn MOnITORInG) 96.9%

3,580 FIT

110 FIT

130 FIT

2,020 FIT

nOTE 1: The table includes consideration to a 246 node system with 6 network Extenders, 14 Physical Layer Repeaters, maximum

cable distance, and a 1-year Proof Test Interval (nFPA 72 requirement) with usage of less than 65% of the SIL 2 budget.

nOTE 2: One EDIO provides both the input channel and the output channel.
nOTE 3: For complex modeling of the EQP System, reference the exida

®

tool at www.exida.com.

Table 1—EQP SIL 2 Safety Function Model - Example