5.1

95-8599

9

S3 Password Protection
The user must define what measures are to be applied to

protect against project changes. S

3

provides safeguards

described in the following paragraphs.

Access to the S

3

software program is restricted by

password protection. Passwords can be changed at any

time by the user with correct privileges.

S

3

supports up to 63 unique user accounts, each

capable of having a different password and access

privileges. These user accounts are controlled by the S

3

system administrator.

Configuring User Accounts
There are five parameters that are used to configure the

users account.

User Level
A user level between 0 and 65535 is used to determine

what a user can do. Each command or button that a

user can interact with in S

3

has a user level assigned to

it. The higher the number, the higher the “privileges” for

that user. A user level of “0” would allow “browsing” only

with no command capability.

Configure System Enabled
When selected, this option allows the user access to

the engineering and configuration aspects of the S

3

software suite. This includes the ability to make, move,

configure and delete ports and the ability to create or

modify points like fire detectors, gas detectors, analog

transmitters, digital inputs, etc. attached to one or more

of the available ports.

Quit “Online” Operations Enabled
When selected, the user is able to quit online operations

and return to the S

3

main screen for access to the

various engineering and maintenance utilities.

Port Diagnostics Viewing Enabled
When selected, when online the user can access

the port diagnostics screen. This screen allows the

user to view details about the operation of all active

communication ports, whether serial or ethernet. This

would typically be used by a technician responsible for

troubleshooting connectivity between the S

3

station and

any attached systems.

Restricted Access Enabled
This feature is intended to give limited access of the

EQP port configurations for viewing and documentation

purposes.

User accounts can be created with only the “restricted

access” checkbox selected, or combined with the

other checkboxes — configure system, quit online, port

diagnostics.

S3 Change Control Log
S

3

maintains a Configuration Log that records changes in

the master project file. The log can be viewed from S

3

.

A record is made in the Configuration Log when:
• IO Modules are added, deleted, or moved
• Tags are added to, removed from, or moved within an

IO Module

• IO Configuration parameters are saved
• External node numbers are entered or modified
• Serial communications parameters are entered or

modified

• A successful download is made to a Controller
• A project is removed.

S3 function Block Logic
The S

3

software allows users to customize application

software with the use of function block logic. For SIL

certified systems, SIL rated function blocks must be

used to comply with the SIL-2 certification.

The SIL rated function blocks and associated input and

output links are color coded red to help the user identify

quickly if there are any non-compliant blocks. Refer to

Appendix B for a list of available function blocks.

Clearly separate safety-related function logic from

non-interfering logic. Place all safety functions on their

own logic pages, and place all non-interfering functions

on their own logic pages.

Note

It is the user’s responsibility to test, verify and
validate all safety related custom logic for
conformance to the code.