The safety related functions of the EQP Safety System

include the following:
– Trouble annunciation for compromised safety function

by de-energizing the Controller’s Trouble relay

– Digital input for lockout of inhibits.

The EQP Safety System employs a 1oo1D (i.e. 1 out of

1 with diagnostics) architecture to achieve SIL 2. EQP

Safety Controllers may be used in redundant mode to

increase system availability, but this is not required for

the safety-related performance of the system.

Configuring and programming the EQP Safety System

must be via a software program known as Safety System

Software (S

3

).

In addition to completing the actions specifically related

to the EQP Safety System, it is necessary to satisfy the

wider requirements of IEC 61508. This includes such

elements within the framework of the safety lifecycle,

such as hazard and risk analysis and defining the safety

instrumented function. This work must be carried out

through appropriate and competent Safety Management

procedures and staff.

DOCUMENT STRUCTURE
This Safety Manual describes the actions that must

be taken to use the Det-Tronics EQP Safety System in

safety-related applications. The main sections are as

follows:

Introduction

Product Overview

gives an overview of the Det-Tronics

product range in general and the EQP Safety products in

particular.

Proof Testing

describes the proof testing that is

necessary.

Suitable Applications

describes the use of the

Det-Tronics EQP Safety System in practical applications.

Included are failure rate data and PFDavg calculations.

Appendix A

provides a summary of the essential data

for safety applications for the Det-Tronics EQP Safety

System.

Appendix B

gives logic instructions and their restrictions

for low demand SIL 2 applications.

PRODUCT OVERVIEW

EQP SYSTEM
The EQP System (on which the Det-Tronics EQP Safety

System is based) was originally developed to meet the

requirements of industrial fire and gas detection and

mitigation. The system comprises (see Figure 1):

• Input / output modules
• Field devices for fire and gas detection
• Controllers which can be programmed to carry out the

control of the fire and gas system

• Power supplies and other miscellaneous hardware
• S

3

software which is used to configure the system and

to generate the logic programs which will be run by

the Controllers

• A proprietary protocol known as Eagle Quantum

Premier Safety Loop (EQPSL), which provides

communication between field devices and the

Controllers.

Note

For additional information regarding set-up and
installation of the eQP system, refer to the eQP
system manual, form number 95-8533.

EQP SAfETY SYSTEM
The Det-Tronics EQP Safety System uses the following

specifically developed components (see Figure 2):
• EQ3XXX – EQP Controller
• EQ3730EDIO – Enhanced Discrete Input/Output

(EDIO) Module

• EQ3710AIM – Analog Input Module
• X3301 – Multispectrum IR Flame Detector
• PIRECL – Infrared Gas Detector

The data required to establish the suitability of the EQP

Safety System for safety-related applications is given in

Appendix A of this Safety Manual.

EQP Safety System components and standard

components can be used together. The non-safety

certified components are classed as non-interfering. A

list of all the devices available for the EQP system is

maintained at www.det-tronics.com and is shown below.