beautypg.com

8599-5.1 (eqp_safety), Safety manual eagle quantum premier, Sil 2 rated fire & gas system – Det-Tronics EQP Fire and Gas Detection/Releasing System SAFETY MANUAL User Manual

Page 3

background image

Note

Where a definition of the term or abbreviation
is given in IeC 61508-4 “Definitions and
Abbreviations”, the definition from the standard is
given first in quotation marks, followed by further
explanation if this is necessary.

INTRODUCTION

This Safety Manual describes the actions that must be

taken to use the Det-Tronics Eagle Quantum Premier

®

(EQP) Safety System in safety-related applications.

The actions that are described can be either technical

or procedural. For example, a procedural action

would be the need to maintain password protection

of configuration programs, so that non-approved staff

cannot modify these.

This document is limited to those actions that are

required to ensure compliance with the relevant safety

certifications and standards. Other documents such

as Manuals and Data Sheets must be referred to for

information outside the scope of this document. These

documents can be found on the Det-Tronics website

www.det-tronics.com.

The Safety Manual is approved and certified by exida

®

as part of the overall EQP Safety System. Satisfying the

requirements it describes is a necessary part of using

the EQP Safety System in safety-related applications.

Failure to complete the actions described in this

document would contravene the certification

requirements.

Completing the actions described in this document will

only satisfy some of the requirements defined by IEC

61508 for safety-related applications.

It will be necessary to satisfy the full requirements

of IEC 61508, and for Process Industry applications,

the requirements of IEC 61511, in order to use the

Det-Tronics EQP Safety System in safety-related

applications.

Further, it is the responsibility of the user to ensure

that the EQP Safety System is suitable for the chosen

application and complies with the appropriate

application standards.

QUALITY POLICY STATEMENT
All quality assurance control measures necessary for

safety management as specified in IEC 61508 Part

1 have been implemented. The quality management

system of Det-Tronics is based on the requirements

of EN ISO 9001 and ANSI/ASQC Q9001 through the

application of the United Technologies Company

Achieving Competitive Excellence (ACE) program. In

addition, the Quality Management System complies

with the European ATEX Directive requirements per EN

13980, the International Electrotechnical Commission

requirements per OD005/V2, and the supervised testing

requirements per ISO 17025.

SCOPE
The Det-Tronics EQP Safety System is intended for use

as part of a programmable electronic system as defined

by IEC 61508. It is suitable for low demand safety

functions up to safety integrity level 2 (SIL 2).

The safety critical functions for the EQP Safety System

include the following:
– Fire input from X3301 and/or EDIO and/or AIM
– Gas alarm from PIRECL and/or EDIO and/or AIM
– Annunciation/Release from EDIO
– System logic for processing and mapping inputs and

outputs.

SAfETY MANUAL

Eagle Quantum Premier

®

SIL 2 Rated Fire & Gas System

5.1

©

Detector Electronics Corporation 2013

Rev: 3/13

95-8599