beautypg.com

Det-Tronics OPECL Infrared Hydrocarbon Gas Detector User Manual

Page 6

background image

4

95-8556

10.1

OpERaTINg mODES
The OPECL has four operating modes: warm-up,

normal, alignment and calibrate.

Warm-up
Warm-up mode is entered upon application of 24 Vdc

operating power. During warm-up, the 4-20 mA current

loop output will indicate warm-up, the indicating LED is

yellow, and the alarm outputs are disabled. The warm-

up mode lasts nominally two minutes after power-up.

Normal
After warm-up mode is completed, the device

automatically enters the Normal mode, and all analog

and alarm outputs are enabled.

alignment
The OPECL modules must be properly aligned before

normal operation is attained. There are two alignment

procedures:

1. Basic Alignment requires the OPECL Alignment Kit.

2. Fine Alignment requires the OPECL Alignment Kit

and a handheld HART Communicator.

Calibrate

After alignment is completed, zero calibration is

required. Span calibration of the OPECL is normally

not required; however, the user has the option to verify

proper calibration or to perform calibration procedures if

necessary. It is recommended that the zero calibration

procedure be performed annually. Refer to the

"Calibration" section in this manual for details.

4-20 ma CURRENT lOOp OUTpUT
OPECL provides a linear current loop output that is

proportional to the detected gas level. Fault and

calibration status are also indicated by this output.

The factory default for full-scale 5 LFL-meters output

is 20 mA. MODBUS interfaces also have the ability to

calibrate the 4 mA and 20 mA levels.

EQP models use LON communication, and do not have

a 4-20 mA output.

PLACE CALIBRATION MAGNET
HERE TO ACTIVATE INTERNAL
REED SWITCH

B2349

Figure 2—Location of Receiver's Internal Magnetic Switch

Default

Configurable Options

Gas Type

Methane

Ethane, Propane

Butane, Propylene

Special

Measurement Range

0-5

0-2, 0-5

(LFL-M)

Low Alarm Threshold

1

0.25 to 3

(LFL-M)

High Alarm Threshold

2

1 to 3

(LFL-M)

Beam Block Delay

60 Seconds

3600 Seconds

Fault Mode

OPGD-Rx

PIR9400, User Defined

Table 2—Factory Default Settings