10.1

StaRtup

When the OPECL is installed and wired as described in

the “Installation” section, it is ready for commissioning.

If the application requires that specific changes be

made to the factory settings, HART communication will

be required.

noTe

ensure that alarm devices are bypassed during
commissioning.

noTe

The safety function (gas input‑to‑actuation/
notification) must always be verified upon
completion of installation and/or modification.

aliGnmEnt

OvERvIEW
The OPECL modules must be properly aligned before

normal operation will be attained. Alignment consists of

a basic alignment stage and a fine alignment stage:

1. basic alignment procedure. This procedure

requires the Telescope Alignment Kit p/n 009104-

001. It does not require a handheld HART Field

Communicator.

2. fine alignment procedure. This procedure requires

a handheld HART Field Communicator with the

OPECL Device Descriptor (DD) software driver (refer

to Appendix F). The fine alignment procedure is

required whenever maximum optical signal strength

is required.

noTe

Basic Alignment must be successfully completed
before attempting Fine Alignment.

noTe

Refer to the FM, ATeX, or IeCex Appendix for
information regarding the effect of misalignment on
system accuracy.

Important

Upon completion of system alignment, ensure that
aLL bolts on the oPeCL mounting bracket are
properly tightened, including the two on the back
side.

baSIC alIgNmENT pROCEDURE

Equipment Required
1. Properly installed and powered OPECL system

(transmitter and receiver). Easy access to both

modules is highly recommended.

2. Telescope Alignment Tool p/n 009104-001. The

telescope alignment tool is recommended for use in

commissioning all OPECL systems. The following

instructions cover the use of the Telescope Alignment

Tool.

3. Calibration Magnet.

4. For installations with module separation distances

between 5 and 30 meters, the range reduction

aperture kit (supplied) is required. Refer to “Aperture

Kit for Short Range Applications” section in this

manual for details.

Remove operating power from the OPECL Transmitter,

and then complete the following steps:

1. Ensure that the system modules are located within

the specified separation range and securely fixed

to the support structures. Bypass all external gas

alarm devices that are connected to the receiver

outputs.

2. Ensure that the system modules are installed with

their windows at approximately the same height

above grade. Each module should be roughly

aligned to face in the direction of the other module.

3. Loosen the locking nuts on the alignment adjuster

bolts so that the bolts can be freely tightened or

loosened for alignment purposes. Loosen, then

hand-snug the two vertical alignment locking nuts.

See Figure 18. At this point, the unit should be easily

adjustable in the vertical and horizontal positions

with little or no adjustment slop.

4. Hand-tighten all four adjustment bolts until the

alignment plate is stabilized.

5. Loosen the brow assembly and slide it toward the

rear of the module.