Det-Tronics OPECL Infrared Hydrocarbon Gas Detector User Manual

Page 37

background image

95-8556

10.1

Special Conditions for Safe Use for the [ib] HART communication port only:

• The intrinsically safe output on the HART Communicator Port is internally connected to frame.

• When connecting to a circuit using up to 1% of Co or Lo, then the C or L is limited to the Co and Lo listed above. If

either the C or L is above 1% of Co or Lo, then C or L are each limited to 50% of the Co or Lo listed above.

• Um is restricted to 250 V, prospective short circuit current < 1500 A.
• The Infrared Hydrocarbon Gas Detectors shall be powered from a SELV isolating transformer and the fuse for Isc

shall be of the type complying with IEC60127.

WARNING

Always ensure that the detector/junction box hazardous (classified) location ratings are applicable for the
intended use.

Additional Safety Notes:

• For ambient temperatures below –10°C, use field wiring suitable for the expected conditions, and for ambient

temperatures above +60°C, use field wiring suitable for 20°C above the maximum expected conditions.

AccurAcy

(per IEC 60079-29-4)

4-20 mA Model: ±0.25 LFL-meters or ±12.4% of applied gas concentration, whichever is greater, with water

vapor @ ≥82°C.

EQP Model:

±0.25 LFL-meters or ±15.2% of applied gas concentration, whichever is greater, @ –55°C.

response tiMe

4-20 mA Model

T50: 1.2 seconds (2.5 LFL-meters applied)

T90: 2.5 seconds (2.5 LFL-meters applied).
EQP Model

T90: 5.3 seconds* (2.5 LFL-meters applied).
* For EQP model only, average of three consecutive trials, with the minimum and maximum response times no

greater than ±2 seconds from the average indicated response time.

AlignMent
Misalignment will cause the manufacturer stated accuracy limits to increase, but remain within the limits of

IEC 60079-29-4.

D-2