beautypg.com

Operation – Det-Tronics OPECL Infrared Hydrocarbon Gas Detector User Manual

Page 5

background image

3

95-8556

10.1

COmmUNICaTION
The standard OPECL system provides an analog 4-20

mA signal output, with HART and RS-485 MODBUS serial

communication from the receiver module. EQP Models

communicate with the EQP controller over the LON.

RECORDINg CapabIlITy
Non-volatile memory is provided to save the 10 most

recent calibrations, alarm/fault events, and minimum/

maximum operating temperature history. A real time

clock is provided to record operating service time and to

time stamp events. This information is accessible using

HART and MODBUS communication, or S3 software for

EQP models.

DETECTION RaNgE
The standard OPECL system can cover a range of 5 to

120 meters.

opERation

mODUlE IDENTIfICaTION
While the OPECL transmitter and receiver modules

appear physically identical, each module is labeled as

“transmitter” or “receiver” on the enclosure. The physical

mounting requirements for both modules are generally

identical. However, there are functional and electrical

characteristic differences as identified in Table 1.

Table 1—Functional and Electrical Comparison of Transmitter and Receiver

Characteristic

Transmitter (Tx)

Receiver (Rx)

Functional Description

Contains primary and backup xenon
flashlamps, and generates optical
energy to enable hydrocarbon
detection.

Contains opto-electronics, signal processing and
output drivers, and diagnostic electronics.

Power Consumption

5.0 watts nominal @ 24 Vdc.
5.8 watts peak @ 24 Vdc.

6.0 watts nominal @ 24 Vdc (without relays).
6.4 watts nominal @ 24 Vdc (with relays).

Electrical Connections

2 power connections only.
(+24 Vdc and –24 Vdc).

From 3-7 connections depending upon specific
configuration (separate power and signal cables
recommended).

Onboard HART Communication
Port

N/A

Connection to handheld HART communicator for
system setup, commissioning, and diagnostics.

Onboard LED Indicator

Indicates normal, fault, and backup
lamp operation status.
Green indicates normal operation.
Yellow indicates operation in “back-up
lamp” mode or other fault condition.

Indicates normal, alarm, fault, and calibration status.
Green indicates normal operation. Blinking red
indicates low gas alarm condition.
Steady red indicates high gas alarm condition.
Yellow indicates operation in “back-up lamp” mode
or system fault.
Calibration status is indicated by a steady red
indication after Calibration command.
LED operation for fault status is non-latching. LED
operation for gas alarms is configurable for latching/
non-latching.

Magnetic Calibration Switch
(See Figure 2 for switch location.)

Momentary activation overrides back-
up lamp fault flash coding sequence,
permitting normal receiver operation
with back-up lamp.

Momentary activation provides reset function for
latched alarm outputs. Activation for longer than 2
seconds will initiate zero calibration.

Factory Default Settings

No programmable options

Factory calibrated for methane, 0-5 LFL-meters
full scale. See Table 2 for receiver factory default
settings. HART communication is required to
change the factory default settings.