CalIbRaTION OvERvIEW
Although routine calibration of the OPECL is normally

not required, the device supports non-intrusive field zero

calibration capability. Span calibration is not required.

zero Calibration
Zero Calibration is a one-step process consisting of clean

air (zero) condition adjustment only, which is performed

automatically by the device. This procedure adjusts

the "clean air" signal output only, and is normally used if

the 4 milliampere signal level has drifted. The cause of

drift is typically due to the presence of background gas

during calibration. Ensure that the optical path is clear

of hydrocarbons prior to calibration initiation to ensure

an accurate zero (clean air) condition.

ImpORTaNT CalIbRaTION NOTES

noTe

ensure that the detector has been operating for at
least two hours before calibrating.

noTe

Always ensure that the oPeCL optics are totally
free of all hydrocarbons before initiating calibration.

CalIbRaTION INITIaTION
Calibration may be initiated by any of the following

means:
• The onboard magnetic calibration switch
• Digital communication via MODBUS communication

(consult factory for details)

• Remote calibration line.
• EQP Point Display

Calibration Using magnetic Switch
The Open Path Eclipse receiver provides an onboard

magnetic calibration/reset switch for non-intrusive

calibration capability. The magnetic switch is actuated

by holding a calibration magnet at the specified location

on the device bulkhead. See Figure 2 for switch

location. An onboard tri-color LED provides status

indication during calibration.

For zero calibration, the magnetic switch must be

actuated for 2 seconds to initiate calibration (signaled

by a solid red LED). Upon initiation, the OPECL

automatically performs the zero calibration adjustment,

and then signals with a green LED when this operation

is complete.

Digital Communication Calibration
MODBUS communication may be utilized to initiate

OPECL calibration (consult factory).

DETaIlED CalIbRaTION pROCEDURE USINg
magNETIC SWITCh

zero Calibration
1. Apply magnet for 2 seconds minimum to initiate

calibration. (Hold the calibration magnet against the

side of the receiver at the location shown in Figure 2.)
A. The onboard LED turns to steady red.
B. The current output decreases to 1 mA in

OPGD-Rx mode or 2.2 mA in PIR9400 mode.

2. When zero calibration is complete:

A. The onboard LED changes from steady red to

steady green.

B. Calibration is complete and current output returns

to 4 mA.

When calibrating an EQP model, calibration status is

indicated on the EQP Point Display screen.

maintEnancE

WarnIng

Do not open cover when an explosive gas
atmosphere may be present.

noTe

Refer to the Model oPeCL Safety Manual
(number 95‑8665) for specific requirements
and recommendations applicable to the proper
installation, operation, and maintenance of all
SIL‑Certified oPeCL IR gas detectors.

ROUTINE INSpECTION
The OPECL detector should be inspected periodically to

ensure that external obstructions such as plastic bags,

mud, snow, or other materials do not block the path and

thereby impair the performance of the device.