beautypg.com

Det-Tronics OPECL Infrared Hydrocarbon Gas Detector User Manual

Page 20

background image

18

95-8556

10.1

6. Install the Telescope Alignment Tool onto

the receiver module by inserting the captive

thumbscrews into the threaded holes on the

faceplate. See Figure 19. Ensure that the telescope

is properly attached, that the eyepiece is accessible,

and that the thumbscrews are completely tightened.

7. Slowly adjust the receiver module up/down as

required using the vertical adjustment bolts until

the telescope cross hairs are centered as close

as possible to dead center on the window of the

transmitter module. Tighten the vertical alignment

locking nuts so that no movement will occur.

VERTICAL ALIGNMENT LOCKING NUTS (2)

VERTICAL ADJUSTMENT
BOLTS WITH LOCKING NUTS (2)

HORIZONTAL ADJUSTMENT
BOLTS WITH LOCKING NUTS (2)

B2302

U-BOLT NUTS (2)*

U-BOLT NUTS (2)*

OPECL MOUNTING BOLT*

OPECL MOUNTING BOLT*

*TORQUE TO 20 FT-LBS

Figure 18—OPECL Mounting and Alignment Hardware (Transmitter Module Shown)

TEMPORARILY SLIDE BROW TOWARD
BACK OF MODULE HOUSING

TELESCOPE ALIGNMENT TOOL

CAPTIVE SCREWS (2)

D2303

TELESCOPE ALIGNMENT SCREW

(VERTICAL)

TELESCOPE ALIGNMENT SCREW

(HORIZONTAL)

Figure 19— OPECL with Telescope Alignment Tool Installed (Transmitter Module Shown)