10.1

F-3

95-8556

ConneCTions And HARdwARe
The HART Communicator can interface with the Open Path Eclipse from the onboard I.S. communication port,

from the control room, or from any wiring termination point in the analog output signal loop. To communicate,

connect the HART communicator in parallel with the Open Path Eclipse analog signal or load resistor. The con-

nections are non-polarized.

Note

the HARt Communicator needs a minimum of 250 ohms resistance in the loop to function properly. the
HARt Communicator does not measure loop current directly.

On EQP models, the HART communicator must be connected to the I.S. communication port.

online menu
When HART communication is established with the receiver, the first menu displayed is the OPGD RX Root

menu:

To select any of the 5 menu options shown, highlight the desired option using the up/down arrow key, and then

press the “right arrow” key.

Commonly used HART CommAnds

The most commonly used HART commands for the Model OPECL are:

1. Setting the real time clock
2. Setting alarm thresholds & latch/nonlatch functions
3. Setting the analog fault code menu
4. Performing full system alignment
5. Performing zero calibration
6. Assigning a nonvolatile tag name to the receiver
7. Defining a nonvolatile descriptor for future reference
8. Interrogating the history menu for information including total running hours, max/min temperature, calibration

and event logs.

OPGD RX Root Menu

1) Process Menu

2) Status Menu

3) Setup Menu

4) Calibration Menu

5) Test Menu

OPGD RX Root Menu

1) Process Menu

2) Status Menu

3) Setup Menu

4) Calibration Menu

5) Test Menu

Status Menu

1) General Info Menu

2) Device Info Menu

3) Sensor Info Menu

4) Fault Status Menu

5) History Menu

Device Info Menu

1) Universal Rev.

2) Field Device Rev.

3) Software Rev.

4) Write Protect

5) RTC Menu

6) Alignment Status Menu

RTC Menu

1) Seconds

2) Minutes

3) Hours

4) Date

5) Month

6) Day

7) Year

8) Write Protect

OPGD RX Root Menu

1) Process Menu

2) Status Menu

3) Setup Menu

4) Calibration Menu

5) Test Menu

OPGD RX Root Menu

1) Process Menu

2) Status Menu

3) Setup Menu

4) Calibration Menu

5) Test Menu

Setup Menu

1) OPGD Option Menu

2) HART Output Menu

3) Com - 485 Menu

4) Config Flt Output Menu

5) Gas Type Menu

6) Range Menu

7) Alarm Menu

8) D/A Trim Method

9) RTC Menu

Alarm Menu

1) High Alarm Level

2) High Alarm Latch

3) Low Alarm Level

4) Low Alarm Latch

OPGD RX Root Menu

1) Process Menu

2) Status Menu

3) Setup Menu

4) Calibration Menu

5) Test Menu

Diag / Test Menu

1) Self Test

2) Response Test

3) Reset

4) Loop Test

5) Debug Menu

6) Alignment Menu

Alignment Menu

1) Quad X

2) Quad Y

3) Reference

4) Enable Alignment

5) Disable Alignment

OPGD RX Root Menu

1) Process Menu

2) Status Menu

3) Setup Menu

4) Calibration Menu

5) Test Menu

OPGD RX Root Menu

1) Process Menu

2) Status Menu

3) Setup Menu

4) Calibration Menu

5) Test Menu

Calibration Menu

1) Gas Type

2) Cal Date

3) User Span Cal Delta

4) Zero Calibration Method