Det-Tronics OPECL Infrared Hydrocarbon Gas Detector User Manual
Page 41
![background image](/manuals/557683/41/background.png)
10.1
F-3
95-8556
ConneCTions And HARdwARe
The HART Communicator can interface with the Open Path Eclipse from the onboard I.S. communication port,
from the control room, or from any wiring termination point in the analog output signal loop. To communicate,
connect the HART communicator in parallel with the Open Path Eclipse analog signal or load resistor. The con-
nections are non-polarized.
Note
the HARt Communicator needs a minimum of 250 ohms resistance in the loop to function properly. the
HARt Communicator does not measure loop current directly.
On EQP models, the HART communicator must be connected to the I.S. communication port.
online menu
When HART communication is established with the receiver, the first menu displayed is the OPGD RX Root
menu:
To select any of the 5 menu options shown, highlight the desired option using the up/down arrow key, and then
press the “right arrow” key.
Commonly used HART CommAnds
The most commonly used HART commands for the Model OPECL are:
1. Setting the real time clock
2. Setting alarm thresholds & latch/nonlatch functions
3. Setting the analog fault code menu
4. Performing full system alignment
5. Performing zero calibration
6. Assigning a nonvolatile tag name to the receiver
7. Defining a nonvolatile descriptor for future reference
8. Interrogating the history menu for information including total running hours, max/min temperature, calibration
and event logs.
OPGD RX Root Menu
1) Process Menu
2) Status Menu
3) Setup Menu
4) Calibration Menu
5) Test Menu
OPGD RX Root Menu
1) Process Menu
2) Status Menu
3) Setup Menu
4) Calibration Menu
5) Test Menu
Status Menu
1) General Info Menu
2) Device Info Menu
3) Sensor Info Menu
4) Fault Status Menu
5) History Menu
Device Info Menu
1) Universal Rev.
2) Field Device Rev.
3) Software Rev.
4) Write Protect
5) RTC Menu
6) Alignment Status Menu
RTC Menu
1) Seconds
2) Minutes
3) Hours
4) Date
5) Month
6) Day
7) Year
8) Write Protect
OPGD RX Root Menu
1) Process Menu
2) Status Menu
3) Setup Menu
4) Calibration Menu
5) Test Menu
OPGD RX Root Menu
1) Process Menu
2) Status Menu
3) Setup Menu
4) Calibration Menu
5) Test Menu
Setup Menu
1) OPGD Option Menu
2) HART Output Menu
3) Com - 485 Menu
4) Config Flt Output Menu
5) Gas Type Menu
6) Range Menu
7) Alarm Menu
8) D/A Trim Method
9) RTC Menu
Alarm Menu
1) High Alarm Level
2) High Alarm Latch
3) Low Alarm Level
4) Low Alarm Latch
OPGD RX Root Menu
1) Process Menu
2) Status Menu
3) Setup Menu
4) Calibration Menu
5) Test Menu
Diag / Test Menu
1) Self Test
2) Response Test
3) Reset
4) Loop Test
5) Debug Menu
6) Alignment Menu
Alignment Menu
1) Quad X
2) Quad Y
3) Reference
4) Enable Alignment
5) Disable Alignment
OPGD RX Root Menu
1) Process Menu
2) Status Menu
3) Setup Menu
4) Calibration Menu
5) Test Menu
OPGD RX Root Menu
1) Process Menu
2) Status Menu
3) Setup Menu
4) Calibration Menu
5) Test Menu
Calibration Menu
1) Gas Type
2) Cal Date
3) User Span Cal Delta
4) Zero Calibration Method