ATEX Special Conditions for Safe Use for the [ib] HART communication port only:

• The intrinsically safe output on the HART Communicator Port is internally connected to frame.
• Um is restricted to 250 V, prospective short circuit current < 1500 A.
• When connecting to a circuit using up to 1% of Co or Lo, then the C or L is limited to the Co and Lo listed above. If

either the C or L is above 1% of Co or Lo, then C or L are each limited to 50% of the Co or Lo listed above.

• The Infrared Hydrocarbon Gas Detectors shall be powered from a SELV isolating transformer and the fuse for Isc

shall be of the type complying with IEC60127.

WARNING

Always ensure that the detector/junction box hazardous (classified) location ratings are applicable for the
intended use.

Additional Safety Notes:

• For ambient temperatures below –10°C, use field wiring suitable for the expected conditions, and for ambient

temperatures above +60°C, use field wiring suitable for 20°C above the maximum expected conditions.

ATEX Standards:
EN 50241-1/A1: 2004
EN 50241-2: 1999
EN 60079-29-4: 2010
Performance Approved for Methane
EN 60079-0: 2009
EN 60079-1: 2007
EN 60079-7: 2007
EN 60079-11: 2007
EN 60529:1991+A1:2000
EN 50270: 2006
EN 50271: 2010

CE: Conforms to:

Low Voltage Directive: 2006/95/EC,

EMC Directive: 2004/108/EC,

ATEX Directive: 94/9/EC, WEEE 2002/96/EC.