beautypg.com

Det-Tronics OPECL Infrared Hydrocarbon Gas Detector User Manual

Page 15

background image

13

95-8556

10.1

pOWER WIRINg SIzE aND maxImUm lENgTh
1. To ensure proper operation, OPECL power terminals

(terminals 1 and 2 for Rx and Tx) and 4-20 mA

terminals (terminals 6 and 7 for Rx) must receive 18

Vdc minimum. 24 Vdc is recommended. Terminals

1 and 4, and terminals 2 and 5 on the OPECL Rx are

internally connected (see wiring diagrams).

2. Always determine voltage drops that will occur to

ensure that 24 Vdc is delivered to the OPECL.

3. Normally, nothing smaller than 18 AWG (1.0 mm

2

)

is recommended by Det-Tronics for OPECL power

cabling.

Wire size requirements are dependent upon power

supply voltage and wire length.

The maximum distance between the OPECL detector

and its power supply is determined by the maximum

allowable voltage drop for the power wiring loop. If the

voltage drop is exceeded, the device will not operate.

To determine the maximum power loop voltage drop,

subtract the minimum operating voltage for the device

(18 Vdc) from the minimum output voltage of the power

supply.

To determine the actual maximum wire length:

1. Divide the maximum allowable voltage drop by the

maximum current draw of the OPECL (0.35 A),

2. Divide by the resistance of the wire (ohms/foot value

available in wire manufacturer’s specification data

sheet),

3. Divide by 2.

For example: Consider an installation using 18 AWG

wiring with a power supply providing 24 Vdc.

Power supply voltage = 24 Vdc,

OPECL minimum operating voltage = 18 Vdc

24 – 18 = 6 Vdc

Maximum Voltage Drop = 6

Maximum Current = 0.35 A

Wire Resistance in Ohms/Foot = 0.006523

6 ч 0.35 ч 0.006523 ч 2 = 1314 feet

OpTIONal RElayS
Optional relay contacts are “dry”, meaning that the

installer must provide the voltage to the common

terminal of the relay output.

AC voltage should not be switched directly using the

OPECL relays. The use of an external relay is required if

AC voltage must be switched by the OPECL relays.

In order to change alarm relay settings from the factory

default settings, it is recommended to utilize a HART

Field Communicator. Contact the factory for further

assistance.

noTe

Refer to “Alarm Relays” in the Specifications section
of this manual for important information regarding
alarm relays.

The relay board must temporarily be removed from

the OPECL termination compartment to connect the

relay output field wiring cables. After the relay wiring

is connected, re-install the relay board using the three

captive screws. Refer to Figure 7.

Note: Relays are not available on EQP models.

FACTORY INSTALLED WIRING

TO RELAY BOARD

(DO NOT REMOVE)

CAPTIVE SCREWS (3)

RELAY TERMINAL BLOCK

A2133

Figure 7—OPECL Wiring Termination Compartment with Optional

Relay Board Removed