CiDRA SONARtrac HD VF-100 User Manual
Page 82
Copyright © 2006 CiDRA Corporation
Page 10-7
20638-02 Rev 01
The following is an example of Pulse settings applied to Total Flow:
Output: Total Flow
Flow Rate: 400 gal/min
Pulse Output: Totalizer
Multiplier: 10
Pulse Width: 1 ms
Low cutoff: 0% or 270.1 gal/m (no cutoff)
In the above example, Pulse output would be 400 gpm / 10 = 40
pulses per minute.
•
Alarm
The transmitter alarm is a tri-state output. The Alarm modes are ‘Off’
(no alarm conditions present) indicated by the transmitter mounted
LED off and no signal being sent to the DCS, ‘Warning’ (an alarm
condition has entered a range of condition(s) where the integrity of
readings may be suspect) indicated by the transmitter mounted LED
and alarm output relay blinking, and ‘Critical’ (an alarm condition in
which the output of the meter can no longer be considered valid)
indicated by the alarm LED on the transmitter being constantly on and
constant relay closure output to the DCS. The measurement result
should be discarded and closed loop controls switched to manual
during a critical alarm.
The alarm can be cancelled either manually or will clear automatically
when the alarm condition is no longer present depending on the menu
option selected (see below).
The following table lists the alarm parameters with their default values.
Alarm Parameter
Condition
User
Entry
Warning
Default Value
Critical
Default Value
TMP>
Y
> 80 °C
> 90 °C
Band Temperature
TMP<
Y
< 0 °C
< 0 °C
SPL>
Y
> 200 dB
> 200 dB
RMS Sound Pressure
Level
SPL<
Y
< 50 dB
< 80 dB
Volumetric Flow Quality
VFQ<
Y
< 0.3
< 0.2
Event log updated
LOG
N
Sensor overload
OVL
N
FLW>
Y
> 30 ft/s
> 30 ft/s
Volumetric Flow or True
Liquid Flow
FLW<
Y
< 3.2 ft/s
< 3 ft/s
Sensor Failure
FAIL
N
Table 16
Alarm Triggers
Note: The alarm trigger for Flow (VF or TLF) can be set from the
transmitter menu. All other values must be set using SONARtrac
Basic (or higher level) user program.