Table 14 Transmitter Menu Tree Software Release 03.03.XX (page 2)

Level 1

Level 2

Level 3

Range

Description

Output Sel

Flow Rate, Blank

Parameter to output

Power Sel

Internal, External

Power supply for 4-
20mA current

Low End

Based on ‘output sel’

Low end output (4mA)

High End

Based on ‘output sel’

High end output (20mA)

Out of Range

Hold, >20mA, <4mA,
4mA

Behavior when meter
reading is out of range
or meter has no reading

Overrange
Rail

Enable, Disable

‘Enable’ causes the
output to go to full
(20mA) or min (4mA)
when system over
ranges

4mA Trim

2 to 6

Adjust 4mA output

4-20mA
Ch1& Ch2

20mA Trim

18 to 22

Adjust 20mA output

Multiplier

0 - 999999

Multiplier on output

Width (ms)

.5,1,20,33,50,100

Pulse width

Lowcut

0% to 100%

Low end cutoff

Pulse

Output Sel

Flow Rate, Totalizer,
Flow Rate%

Parameter to output

Warning Off/On

Activates alarm warning
function

Critical Off/On

Activates alarm critical
function

Alarm
Control

Manual Clear Off/On

Allows for manual or
automatic alarm
clearing

Flw Min

Alarm
Warning
Threshold

Flw Max

0-100% of range

Used to set the
minimum and maximum
values for a warning
alarm

Flw Min

Alarm Critical
Threshold

Flw Max

0-100% of range

Used to set the
minimum and maximum
values for a critical
alarm

State Enable,

Disable Enable noise filtering

Flow Noise
Filter

Magnitude

Low, High

Amount of damping

State

Enable, Disable

Enable Damping

Flow
Damping

Time
Constant (s)

0-600 seconds; default
is 3

Smoothes output due to
rapid changes in flow

State Enable,

Disable Enable spike filtering

Length

2 – 60 readings

# of measurements to
validate

Output Config

Flow Spike
Filter

Percent

0 – 100 %

% of full measurement
range that will define
the spike size to be
rejected