Rockwell Automation 1734-AENT POINT I/O EtherNet/IP Adapter Module User Manual
Page 80

Publication 1734-UM011D-EN-P - May 2011
64 LED Status Indicators
Indication
Probable Cause
Recommended Action
Network Activity
Off
No link established.
Verify network cabling, and correct,
as needed.
Flashing
green/Off
Transmit or receive activity
present.
None
Steady green
Link established.
None
Network Status
Off
Device not initialized. The
module does not have an IP
address.
Apply power to device, verify IP
address, and correct, as needed.
Flashing green No CIP connections present.
Device has an IP address, but no
CIP connections are established.
None
Solid green
CIP connections present. Device
online and has an IP address, and
CIP connections are established.
None
Flashing red
One or more CIP connections has
timed-out.
Check for I/O module failure and
controller operation, and correct, as
needed.
Solid red
Duplicate IP address detected.
Verify IP address setting and correct,
as needed.
Flashing
red/green
The module is performing a
self-test (only occurs during cycle
power test).
None
POINTBus Status
Off
Device not powered – check
module status indicator.
Apply power to device.
Flashing
red/green
LED cycle power test present.
None
Flashing red
Recoverable fault occurred:
• At cycle power the
number of expected
modules does not equal
the number of modules
present
• A module is missing
• Node fault (I/O
connection timeout)
occurred.
• Configure chassis size.
• Check for missing module and
reinstall as needed.
• Check for I/O module failure
and correct as needed.
Solid red
Unrecoverable fault occurred –
the adapter is bus off.
1. Cycle power to device.
2. If condition persists, replace
device.
Flashing green Firmware (NVS) update in
progress.
None
Solid green
Adapter online with connections
established (normal operation,
Run mode).
None