POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 123

1734-SSI

1 Channel Synchronous Serial Interface
Configuration Data

Data Type

Default

Value

Valid Data Values

Run

SINT

1

0=Module Not Running

1=Module Is Running

Gray Binary

SINT

1

0=Binary Code

1=Gray Code

Word Length

SINT

13

2…31

Data Speed

SINT

5

5=125 Kbps

6=250 Kbps

7=500 Kbps

8=1 MB

9=2 MB

G2B Convert (Gray to Binary)

SINT

0

0=No Convert

1=Convert

Standardization

(Divide / Shift using Trailing)

SINT

0

0=No Standardization

1=Apply Standardization

SSI Word Delay Time

INT

64

-32,768…32,767

µs

(16…65,535)

Trailing (No. of Trailing Bits)

SINT

0

0…16

Input Latch Control

InputLatch_0

InputLatch_1

SINT

BIT 0

BIT 1

0

00=Off

01=Falling Edge of Input

10=Rising Edge of Input

11=Both Edges of Input

Sensor Resolution

(Positions per Rev. or Stroke)

INT

1

-32,768……32,767 counts

(1…65,535)

Sensor Cycle

(Total Revolutions or Strokes)

INT

1

-32,768…32,767 counts

(1…65,535)

Compare 0 Value

DINT

0

-2,147,483,648…

2,147,483,647

(0…4,294,967,295)

Compare 1 Value

DINT

0

-2,147,483,648…

2,147,483,647

(0…4,294,967,295)

Compare 0 Control

Compare0_0

Compare0_1

SINT

BIT 0

BIT 1

0

00=Off

01=Up Direction

10=Down Direction

11=Both Directions

Compare 1 Control;

Compare1_0

Compare1_1

SINT

BIT 0

BIT 1

0

00=Off

01=Up Direction

10=Down Direction

11=Both Directions