Rockwell Automation 1734-AENT POINT I/O EtherNet/IP Adapter Module User Manual
Page 137

Publication 1734-UM011D-EN-P - May 2011
POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 123
1734-SSI
1 Channel Synchronous Serial Interface
Configuration Data
Data Type
Default
Value
Valid Data Values
Run
SINT
1
0=Module Not Running
1=Module Is Running
Gray Binary
SINT
1
0=Binary Code
1=Gray Code
Word Length
SINT
13
2…31
Data Speed
SINT
5
5=125 Kbps
6=250 Kbps
7=500 Kbps
8=1 MB
9=2 MB
G2B Convert (Gray to Binary)
SINT
0
0=No Convert
1=Convert
Standardization
(Divide / Shift using Trailing)
SINT
0
0=No Standardization
1=Apply Standardization
SSI Word Delay Time
INT
64
-32,768…32,767
µs
(16…65,535)
Trailing (No. of Trailing Bits)
SINT
0
0…16
Input Latch Control
InputLatch_0
InputLatch_1
SINT
BIT 0
BIT 1
0
00=Off
01=Falling Edge of Input
10=Rising Edge of Input
11=Both Edges of Input
Sensor Resolution
(Positions per Rev. or Stroke)
INT
1
-32,768……32,767 counts
(1…65,535)
Sensor Cycle
(Total Revolutions or Strokes)
INT
1
-32,768…32,767 counts
(1…65,535)
Compare 0 Value
DINT
0
-2,147,483,648…
2,147,483,647
(0…4,294,967,295)
Compare 1 Value
DINT
0
-2,147,483,648…
2,147,483,647
(0…4,294,967,295)
Compare 0 Control
Compare0_0
Compare0_1
SINT
BIT 0
BIT 1
0
00=Off
01=Up Direction
10=Down Direction
11=Both Directions
Compare 1 Control;
Compare1_0
Compare1_1
SINT
BIT 0
BIT 1
0
00=Off
01=Up Direction
10=Down Direction
11=Both Directions