100 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference
Analog 2 Channel Input
1734-IE2C
2 Channel Analog Current Input
Configuration Data
Data Type Default
Value
Valid Data Values
Low Engineering Channel 0
INT
3,277
-32,768…32,767
High Engineering Channel 0
INT
16,383 -32,768…32,767
Digital Filter Channel 0
INT
0
0…10,000 ms
Low Alarm Limit Channel 0
INT
3,113
-32,768…32,767
High Alarm Limit Channel 0
INT
16,547 -32,768…32,767
Low Low Alarm Limit Channel 0
INT
2,867
-32,768…32,767
High High Alarm Limit Channel 0
INT
16,793 -32,768…32,767
Range Type Channel 0
SINT
3
3=4…20 mA
8=0…20 mA
Limit Alarm Latch Channel 0
SINT
0
0=No Latching
1=Alarms Latch
Alarm Disable Channel 0
SINT
0
0=Alarms Enabled
1=Alarms Disabled
Low Engineering Channel 1
INT
3,277
-32,768…32,767
High Engineering Channel 1
INT
16,383 -32,768…32,767
Digital Filter Channel 1
INT
0
0…10,000 ms
Low Alarm Limit Channel 1
INT
3,113
-32,768…32,767
High Alarm Limit Channel 1
INT
16,547 -32,768…32,767
Low Low Alarm Limit Channel 1
INT
2,867
-32,768…32,767
High High Alarm Limit Channel 1
INT
16,793 -32,768…32,767
Range Type Channel 1
SINT
3
3=4-20 mA
8=0-20 mA
Limit Alarm Latch Channel 1
SINT
0
0=No Latching
1=Alarms Latch
Alarm Disable Channel 1
SINT
0
0=Alarms Enabled
1=Alarms Disabled
Notch Filter (Channel 0 & 1)
SINT
2
1=50 Hz
2=60 Hz
4=250 Hz
6=500 Hz
Real-time Sample (Channel 0 & 1)
INT
100
0…10,000 ms