Digital 4 point input – Rockwell Automation 1734-AENT POINT I/O EtherNet/IP Adapter Module User Manual
Page 108

Publication 1734-UM011D-EN-P - May 2011
94 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference
Digital 4 POINT Input
1734-IB4
4 POINT 10…28V DC Input, Sink
1734-IV4
4 POINT 10…28V DC Input, Source
Configuration Data
Data Type
Default
Value
Valid Data Values
Filter Off On Time - POINT 0
INT
1,000
-32,768…32,767
µs
(1)
(0…65,535)
(1)
POINT I/O Modules support the Unsigned Integer data type UINT (0…65,535 range).
RSLogix 5000 software supports the signed Integer data type INT (-32,768…+32,767 range).
To enter Filter values from +32,768…+65,535
µs, use this conversion formula:
Desired Filter Value (in
µs) - 65536 = Entered Filter Value (in µs).
As an example, for a 40 ms filter time, 40000 - 65536 = -25536
Filter On Off Time - POINT 0
INT
1,000
-32,768…32,767
µs
(1)
(0…65,535)
Filter Off On Time - POINT 1
INT
1,000
-32,768…32,767
µs
(1)
(0…65,535)
Filter On Off Time - POINT 1
INT
1,000
-32,768…32,767
µs
(1)
(0…65,535)
Filter Off On Time - POINT 2
INT
1,000
-32,768…32,767
µs
(1)
(0…65,535)
Filter On Off Time - POINT 2
INT
1,000
-32,768…32,767
µs
(1)
(0…65,535)
Filter Off On Time - POINT 3
INT
1,000
-32,768…32,767
µs
(1)
(0…65,535)
Filter On Off Time - POINT 3
INT
1,000
-32,768…32,767
µs
(1)
(0… 65,535)
Input Data
Data Type
Default
Value
Valid Data Values
Input Data - POINT 0, 1, 2, 3
SINT, BIT
0
0=Off
1=On
Output Data
Data Type
Default
Value
Valid Data Values
None