beautypg.com

Notice – Burnham MPC User Manual

Page 73

background image

7

SECTION VII - BURNER SPECIFICATIONS

BOILER

MODEL

BURNER

MIN.

INPUT

(GPH)

BURNER

MAX.

INPUT

(GPH)

BURNER

MODEL

AIR

TUBE

COMB.

BURNER SETTINGS

PUMP

PRESSURE

(PSI)

NOZZLE

MAKE

NOZZLE

DATA

HEAD

LOW FIRE

AIR OR

SHUTTER

HIGH FIRE

AIR OR

BAND

LOW
FIRE

HIGH

FIRE

GPH X

ANGLE

- TYPE

MPC4

1.75

3.55

CF500

CF60KK

3

10

2

N/A

150

Delavan

2.75 X 70 - B

MPC5

3.0

5.5

CF800

CF60KH

3

8.5

0

N/A

150

Delavan

4.50 X 70 - B

MPC6

4.0

7.1

CF1400

CF66KD

4

43

48

150

250

Delavan

4.50 X 60 - B

MPC7

4.0

8.7

CF1400

CF66KE

6

45

51

150

300

Delavan

5.00 X 45 - B

MPC8

7.0

10.2

CF2300

CF66KG

1

37

47

150

300

Delavan

6.00 X 45 - B

MPC9

7.0

11.8

CF2300

CF66KG

7

39

41

150

295

Hago

7.00 X 45 - P

MPC10

7.0

13.4

CF2300

CF66KG

9

43

54

140

280

Delavan

8.00 X 45 - B

MPC11

10.0

15.0

CF2500

CF66KP

2

22

35

275

275

Hago

4.50 X 45 - P

MPC12

10.0

16.6

CF2500

CF66KP

2

23

41

300

300

Hago

5.00 X 45 - P

MPC13

10.0

18.2

CF2500

CF66KP

5

24

38

300

300

Hago

5.50 X 45 - P

MPC14

10.0

19.8

CF2500

CF66KP

6

26

43

275

275

Hago

6.00 X 45 - P

MPC15

10.0

21.5

CF2500

CF66KP

9

25

40

270

270

Hago

6.50 X 45 - P

MPC16

17.0

23.0

CF3500

CF114KR

7

29

42

275

275

Hago

7.00 X 45 - P

MPC17

17.0

24.5

CF3500

CF114KR

8

30

51

275

295

Hago

7.50 X 45 - P

MPC18

17.0

26.0

CF3500

CF114KR

8

29

68

265

265

Hago

8.00 X 45 - P

Table XIIIa: Beckett #2 Oil Burner Specifications

BOILER

MODEL

BURNER

MIN.

INPUT

(MBH)

BURNER

MAX.

INPUT

(MBH)

BURNER

MODEL

DAMPER SETTINGS

MANIFOLD PRESSURE

(“WC)

MINIMUM

INLET

PRESSURE

(“WC)

LOW
FIRE

HIGH

FIRE

SHUTTER

BAND

LOW FIRE

(START)

HIGH

FIRE

MPC4

300

500

CG10.3

N/A

N/A

6

0

1.0

1.8

2.80

MPC5

300

773

CG10.5

N/A

N/A

10

0

1.6

3.2

4.80

MPC6

350

995

CG15.2

26

45

N/A

N/A

1.15

3.15

4.30

MPC7

350

1216

CG15.3

29

66

N/A

N/A

1.1

3.5

4.60

MPC8

550

1438

CG25.1

16

45

N/A

N/A

1.1

3.6

4.70

MPC9

550

1660

CG25.2

22

53

N/A

N/A

0.8

3.57

4.37

MPC10

550

1881

CG25.3

25

54

N/A

N/A

0.75

3.4

4.15

MPC11

550

2103

CG25.4

27

52

N/A

N/A

0.9

3.6

4.50

MPC12

730

2325

CG50.1

28

72

N/A

N/A

0.9

4.2

5.10

MPC13

730

2547

CG50.2

20

39

N/A

N/A

0.8

3.6

4.40

MPC14

730

2769

CG50.3

22

39

N/A

N/A

0.7

3.4

4.10

MPC15

730

2991

CG50.3

22

44

N/A

N/A

0.65

4.0

4.65

MPC16

730

3213

CG50.3

21

46

N/A

N/A

0.6

4.3

4.90

MPC17

730

3435

CG50.4

24

47

N/A

N/A

0.7

4.0

4.70

MPC18

730

3657

CG50.4

25

72

N/A

N/A

0.7

4.9

5.60

Table XIIIb: Beckett Gas Burner Specifications

NOTICE

MPC boiler ratings and capacities are based upon the following burners, pump pressures, nozzle sizes and
manifold pressures. Refer to instructions furnished with burner for additional information regarding proper
installation, fuel piping, wiring details, burner adjustments, service instructions and burner start-up.

This manual is related to the following products: