1

Table V: Minimum Installation Clearances To
Combustible Materials (Inches) per
UL76 (Packaged / Firetested Boiler)

C

A

B

Chimney

D

E

F

Boiler Above

Front

Connector

Rear

Sides

Below

MPC

18

48

18

18

18

NC *

* NC - Noncombustible Flooring

Note: See Table III for recommended service clearance
to access rear of boiler.

NOTE 1: Listed clearances comply with UL 726, Standard
for Oil-Fired Boiler Assemblies.

NOTE 2: MPC Series boilers can be installed in rooms
with clearances from combustible material as listed above.
Listed clearances cannot be reduced for alcove or closet
installations.

WARNING

All boiler builds, except boilers bearing the
UL Label, are suitable for installation on

combustible floor. Do not install boiler on
carpeting.
Floor construction should have adequate
load bearing characteristics to bear the

weight of the boiler filled with water (see
Table 1). A boiler foundation similar to the
one shown in Figure is recommended if

the boiler room floor is weak or uneven or if
a water condition exists.

4. PROVIDE AIR SUPPLY AND VENTILATION to

accommodate proper combustion.

WARNING

Failure to supply adequate air to the boiler will
result in unsafe boiler operation.

For commercial and industrial equipment, permanent
facilities for supplying an ample amount of outside air
shall be provided in accordance with the following.

For boiler rooms adjacent to outside walls, and where
combustion air is provided by natural ventilation from
the outside, there shall be a permanent air supply inlet
having a total free area of not less than 1 sq. in. per
4,000 Btu per hr. (35 sq. in. per gal. per hr.) (5.5 cm2
per kw.) of total input rating of the burner or burners
and in no case less than 35 sq. in. (0.425 m2).

For boiler rooms not adjacent to outside walls, the
combustion air shall be supplied in a manner acceptable
to the authority having jurisdiction.

Figure : Boiler Foundation

3. PROVIDE ADEQUATE FOUNDATION for the

unit. Refer to Figure 2.