Burnham MPC User Manual
Page 72
7
Table XII: Recommended Periodic Testing Check List (continued)
Item
Frequency
Accomplished by
Remarks
High Limit Safety Control
Annually
Service Technician
Refer to instructions
Operating Control
Annually
Service Technician
Refer to instructions
Low Draft, Fan, Air
Pressure, and Damper
Position Interlocks
Monthly
Operator
Refer to burner instructions
High and Low Gas
Pressure Interlocks
Monthly
Operator
Refer to burner instructions
High and Low Oil
Pressure Interlocks
Monthly
Operator
Refer to burner instructions
High and Low Oil
Temperature Interlocks
Monthly
Operator
Refer to burner instructions
Fuel Valve Interlock
Switch
Annually
Service Technician
Refer to burner instructions
Purge Switch
Annually
Service Technician
Refer to burner instructions
Burner Position Interlock
Annually
Service Technician
Refer to burner instructions
Burner Rotary Cup
Interlock
Annually
Service Technician
Refer to burner instructions
Low Fire Start Interlock
Annually
Service Technician
Refer to burner instructions
Automatic Fuel
Changeover Control
(Dual Fuel)
At least annually
Service Technician
Under supervision of gas utility
Safety Relief Valve
As required
Operator
In accordance with procedure in Section
VI, ASME Boiler and Pressure Vessel
Code, Recommended Rules for Care
and Operation of Heating Boilers
Burner Components
Inspection
Semiannually
Service Technician
Refer to burner instructions