SECTION IV - INSTALLATION INSTRUCTIONS

Packaged Boiler Shipping Information

Figure 8: Packaged Boiler Shipping Information

A.

PAcKAGED BOiLER

1. The packaged boiler comes on its own shipping

skid (see Figure 48) and the assembled block is
hydrostatically tested at the factory. Once the boiler

is in its final position, PERFORM ANOTHER
HYDROSTATIC TEST AT 1½ TIMES THE
WORKING PRESSURE OF THE BOILER (see
Section II, Paragraph C). The shipping skid can be
used as a housekeeping pad unless local codes say
otherwise. Most controls are pre-wired down to the
burner. If burner is equipped with a lead lag panel,
lead lag controls will be shipped loose for header
mounting. The power can be supplied to the burner
if equipped with a control panel. If burner has no
panel, the power must be supplied to a junction box
near the front of the boiler.

2. If the boiler burner unit was factory fire tested,

the burner was adjusted to approximately 10.2%

CO2 (gas) or 13.2% CO2 (oil) with an overfire
pressure as listed in Table II of this manual. Final
adjustments should be made once the unit is
installed.

B.

BOiLER PiPiNG - hEATiNG APPLicATiONs

CONNECT SUPPLY AND RETURN PIPING TO
HEATING SYSTEM (see Figures 49a, 49b, 50a and
50b).

WARNING

Failure to properly pipe boiler may result in
improper, unsafe system operation and void
manufacturer’s warranty.

DO NOT improperly pipe boiler.

WARNING

All hot water pipes must have clearances of at
least 1/” from all combustible construction.

WARNING

A hot water boiler installed above radiation level
must be provided with a low water cutoff device
as part of the installation.

1. HOT WATER HEATING - This boiler must be

installed in strict accordance to the instructions
found in this installation manual. Deviations
from these installation instructions may void
manufacturer’s warranty.

* Width can vary with gas train configuration.
** Varies slightly with burner and gas train configuration.

1. Do not tilt. Exercise caution when lifting to avoid

damage.

2. This boiler can be lifted by fork truck. Do not truck from

front.

3. When lifting from rear, forks must extend from beyond

center of gravity and second skid cross bar.

4. When lifting from side, forks must extend to opposite

skid rail and straddle center of gravity.

5. Cablespreader is to prevent jacket damage. Spreader

width should equal B (width of skid) + 12”. Adjust cable
lengths to lift at approximate center of gravity per chart.

Number of

Sections

Length

A

(Inch)

Width

B *

(Inch)

Height

C

(Inch)

Approx.

Center of
Gravity D

** (Inch)

Approx.

Shipping

Weight

(Lbs.)

4

77½

48

61½

23¼

2789

5

83½

48

61½

26¼

3272

6

95½

48

61½

29¼

3755

7

101¾

48

61½

32½

4249

8

108

48

61½

35½

4783

9

114

48

61½

38½

5261

10

130¼

48

61½

44½

5757

11

136½

48

61½

47¾

6236

12

142½

48

61½

50¾

6739

13

148½

48½

61½

53¾

7227

14

154¾

48½

63½

57

7760

15

161

48½

63½

60

8335

16

167

48½

63½

63

8824

17

173

48½

63½

66

9324

18

179¼

48½

63½

69¼

9823