Model MPC™ Boilers

Boiler Model

Boiler Horsepower

Burner Input

Gross Output (MBH)

Net I=B=R Rating

(MBH)

Combustion

Efficiency

Heating Surface

(Sq. Ft.)

Net Furnace V

olume

(Cu. Ft.)

Pressure in Firebox

(Inches Wtr

. Column)

W

ater Content

(Gallons)

Boiler W

eight

w/W

ater (LBS.)

V

ent (Flue Outlet

Damper) Dia.

(Inches)

Oil (GPH)

Oil (MBH)

Gas (MBH)

Oil - %

Gas - %

MPC4

12.7

3.55

497

500

424

369

89.0

86.3

75.0

7.1

0.10

63

2820

7

MPC5

19.5

5.50

770

773

652

567

88.8

86.1

95.3

9.1

0.19

78

3396

7

MPC6

25.0

7.10

994

995

837

728

88.7

86.0

115.5

11.0

0.28

93

3972

8

MPC7

30.6

8.70

1218

1216

1023

890

88.7

86.0

135.8

12.9

0.34

108

4558

8

MPC8

36.1

10.2

1428

1438

1209

1051

88.6

85.9

156.1

14.8

0.39

123

5144

8

MPC9

41.7

11.8

1652

1660

1395

1213

88.6

85.9

176.4

16.7

0.45

137

5721

10

MPC10

47.2

13.4

1876

1881

1580

1374

88.6

85.9

196.6

18.6

0.50

152

6307

10

MPC11

52.8

15.0

2100

2103

1766

1536

88.5

85.9

216.9

20.6

0.66

167

6893

10

MPC12

58.3

16.6

2324

2325

1951

1697

88.5

85.8

237.2

22.5

0.82

182

7489

12

MPC13

63.8

18.2

2548

2547

2137

1858

88.5

85.8

257.5

24.4

0.98

196

8077

12

MPC14

69.4

19.8

2772

2769

2322

2019

88.5

85.8

277.7

26.3

1.14

211

8673

12

MPC15

74.9

21.5

3010

2991

2508

2181

88.4

85.8

298.0

28.2

1.30

226

9269

12

MPC16

80.5

23.0

3220

3213

2694

2343

88.4

85.8

318.3

30.2

1.30

241

9865

12

MPC17

86.0

24.5

3430

3435

2880

2504

88.4

85.8

338.6

32.1

1.40

256

10470

12

MPC18

91.6

26.0

3640

3657

3065

2665

88.4

85.8

358.8

34.0

1.50

270

11068

12

(1) Suffix “N” indicates natural gas-fired, suffix “P” indicates LP gas-fired, “O” indicates oil-fired, “C” indicates combination natural

gas/oil-fired, “D” indicates combination LP gas/oil-fired.
(2) I=B=R net ratings shown are based on 1.15 piping and pickup factor for water.

Consult manufacturer for installations having unusual piping and pickup requirements, such as intermittent system operation,
extensive piping systems, etc.

(3) The I=B=R burner capacity in GPH is based on oil having a heat value of 140,000 BTU per gallon.

(4) Boiler ratings are based on 13.2% CO

2

(oil) and 10.2% CO

2

(natural gas) and +.10” water column pressure at boiler flue

outlet.

Ratings shown above apply at altitudes up to 1000 feet on oil and 2000 feet on gas. For altitudes above those indicated, the
ratings should be reduced at the rate of 4% for each 1000 feet above sea level.

Safety Relief Valve Set Pressure: Standard - 50 PSI; Optional - 30 PSI, 80 PSI

TABLE II: RATINGS/DATA