Figure 50a: Alternate MPC Minimum Piping - Single Boiler Application

Boiler

Model

Supply / Return

20°F Rise

40°F Rise

Nom. I.D.

(Inch)

Water Side

Press. Drop

(Ft/Wtr)

Flow
Rate

(GPM)

Nom. I.D.

(Inch)

Water Side

Press. Drop

(Ft/Wtr)

Flow
Rate

(GPM)

MPC4

2

1.9

42.4

0.9

21.2

MPC5

2

2.6

65.2

1.6

32.6

MPC6

2

3.3

83.7

2.3

41.9

MPC7

4.0

102.3

3.0

51.2

MPC8

4.7

120.9

2

3.7

60.5

MPC9

3

5.4

139.6

2

4.4

69.8

MPC10

3

6.1

158.1

2

5.1

79.0

MPC11

3

6.8

176.7

2

5.8

88.3

MPC12

3

7.5

195.2

6.4

97.6

MPC13

4

8.2

213.8

7.1

106.9

MPC14

4

8.9

232.3

7.8

116.1

MPC15

4

9.6

250.9

8.5

125.5

MPC16

4

10.3

269.5

3

9.2

134.8

MPC17

4

11.0

288.1

3

9.9

144.1

MPC18

4

11.7

306.6

3

10.6

153.3

1

Boiler Operating Requirements:

• Minimum Return Water Temperature = 80°f

• Maximum Delta T = 80°f

• Minimum supply Water Temperature = 130°f

NOTES:

1. All piping is schedule 40.

2. Pipe sizes listed are based on a 20° F

or 40° F Delta T (temperature rise
across the boiler).

Select one to match application.

3. When specified piping size is less than

4”, install appropriate size reducer
directly onto boiler supply and return
manifolds.

4. Drain valve - ball valve preferable,

gate valve acceptable alternative
(supplied by others). Minimum valve
size per ASME code is 3/4” NPT.

5. Swing joints may be piped over the top

of the boiler if space is limited.

6. System design must accommodate the

above Boiler Operating Requirements.

7. Diaphragm expansion tank shown, but

other types of air elimination systems
may be used.