Commissioning, Startup, Operation, and Shutdown

CAUTION:

• The pump and system must be free of foreign objects. If pump becomes plugged, shut down and

unplug prior to restarting pump.

• Avoid excessive vibration levels. Excessive vibration levels can damage the bearings, stuffing box

or seal chamber, and the mechanical seal, which can result in decreased performance.

• Avoid increased radial load. Failure to do so can cause stress on the shaft and bearings.
• Avoid heat build-up. Failure to do so can cause rotating parts to score or seize.
• Avoid cavitation. Failure to do so can cause damage to the internal surfaces of the pump.

Operation under freezing conditions

NOTICE:
Do not expose an idle pump to freezing conditions. Drain all liquid that is inside the pump and
the cooling coils. Failure to do so can cause liquid to freeze and damage the pump.

Temperature ratings

CAUTION:
Do not operate the pump above the rated temperature range of the magnets. This will weaken or ruin the
magnets. The rated temperature is 250°F (121°C) for all sizes.

Magnetic types

Drive destination

Rated temperature

Neodymium iron (NdFe)

A, B, C, D, E, F, G, H, I, J, K

356°F (180°C)

Samarium Cobalt (SmCo)

AA, BB, CC, DD, EE, FF, GG, HH, 536°F (280°C)
II, JJ, KK

Shut down the pump

WARNING:
The pump can handle hazardous and toxic fluids. Identify the contents of the pump and observe proper
decontamination procedures in order to eliminate the possible exposure to any hazardous or toxic fluids.
Wear the proper personal protective equipment. Potential hazards include, but are not limited to, high
temperature, flammable, acidic, caustic, explosive, and other risks. You must handle and dispose of
pumped fluid in compliance with the applicable environmental regulations.

1. Slowly close the discharge valve.
2. Shut down and lock the driver to prevent accidental rotation.

Make the final alignment of the pump and driver

WARNING:

• Always disconnect and lock out power to the driver before you perform any installation or

maintenance tasks. Failure to disconnect and lock out driver power will result in serious physical
injury.
• Electrical connections must be made by certified electricians in compliance with all international,

national, state, and local rules.

• Refer to driver/coupling/gear manufacturers installation and operation manuals (IOM) for specific

instructions and recommendations.

• Follow shaft alignment procedures in order to prevent catastrophic failure of drive components or

unintended contact of rotating parts. Follow the coupling installation and operation procedures from
the coupling manufacturer.

You must check the final alignment after the pump and driver are at operating temperature. For
initial alignment instructions, see the Installation chapter.

Model 3296 EZMAG Installation, Operation, and Maintenance Manual