beautypg.com

Lbd - loop break detection alarm, Safe output value with sensor failure, Usb interface – NOVUS Controller N120 User Manual

Page 4: Instalation

background image

NOVUS AUTOMATION

4/14

When the application requires both heating and cooling at the same

time, you must set the parameters ACt=re and adjust the overlap

(OLAP) to determine the type of operation.
There are three situations:
OLAP

> 0; when there are overlapping between heating and cooling

actions.

Control output

Process variable

Overlap

Pb1

Pb2

Output 1

Output 2

Set Point

OLAP

< 0; for setting a dead-band.

Control Output

Process Variable

Dead band

Pb1

Pb2

Output 1

Output 2

SetPoint

OLAP

= 0; no superposition or dead-band for the outputs.

Control Output

Process Variable

Pb1

Pb2

Output 1

Output 2

Set Point

Output 2 has independent proportional band and PWM period, as

well as maximum and minimum limits for the output.
If Pb2=0, the control #2 becomes ON-OFF.
Both outputs can be on at the same time even with negative OLAP if

Control Output 1 is using PID control.

Control Output

Process Variable

Pb1

HIST2

Output 1

Output 2

OFF

ON

Set Point

LBD - LOOP BREAK DETECTION ALARM
The parameter defines a time interval, in minutes, within which the

PV is expect to react to a control output signal. If the PV does not

react properly within the time interval configured in lbd.t, the

controller interprets this as a control loop break and signals this

occurrence in the display.
A LBD event may be sent to any I/O channel. Simply configure the
LDB function to the desired I/O channel: the selected output will be

activated when a LDB condition is detected. When the lbd.t

parameter is programmed with 0 (zero), the LDB function is disabled.
The LDB is useful in system supervision and troubleshooting, allowing

early detection of problems in the actuator, power source or load.

SAFE OUTPUT VALUE WITH SENSOR FAILURE
(Output 1 only)
This function defines an output value (user defined) to be assigned to

the control output in the event of a sensor failure.
When the input sensor is identified as broken, the controller switches

the control mode to MANUAL while forcing MV to assume the user

configured value in the 1E.ov parameter.
This function requires that one of the alarms be configured as 1Err

and the 1E.ov parameter (control output percentage) programmed

with a value other then 0 (zero).

Once this function is triggered, the controller remains in SAFE mode

(MANUAL control output) even after the sensor failure appears to be

fixed. The operator intervention is required for switching back to

AUTO mode.

USB INTERFACE
The USB interface is used for CONFIGURING or MONITORING the

controller. The NConfig software must be used for the configuration.

It makes it possible to create, view, save and open configurations

from the equipment or files in your computer. The tool for saving and

opening configurations in files makes it possible to transfer

configurations between pieces of equipment and to make backup

copies. For specific models, the NConfig software also makes it

possible to update the firmware (internal software) of the controller

through the USB.
For MONITORING purposes you can use any supervisory software

(SCADA) or laboratory software that supports the MODBUS RTU

communication on a serial communications port. When connected to

the USB of a computer, the controller is recognized as a conventional

serial port (COM x). Use the NConfig software or consult the

DEVICE MANAGER in the Windows CONTROL PANEL to identify

the COM port that was assigned to the controller. Consult the

mapping of the MODBUS memory in the controller’s communications

manual and the documentation of your supervisory software to

conduct the MONITORING process.
Follow the procedure below to use the USB communication of the

equipment:
• Download the NConfig software from our website and install it on

your computer. The USB drivers necessary for operating the

communication will be installed together with the software.

• Connect the USB cable between the equipment and the

computer. The controller does not have to be connected to a

power supply. The USB will provide enough power to operate the

communication (other equipment functions cannot operate).

• Open the NConfig software, configure the communication and

start recognition of the device.

• Consult the NConfig help desk for detailed instructions about how

to use it and solve problems.

The USB interface IS NOT SEPARATE from the

signal input (PV) or the controller’s/indicator’s digital

inputs and outputs. It is intended for temporary use

during CONFIGURATION and MONITORING

periods. For the safety of people and equipment, it

must only be used when the piece of equipment is

completely disconnected from the input/output

signals. Using the USB in any other type of

connection is possible but requires a careful analysis

by the person responsible for installing it. When

MONITORING for long periods of time and with

connected inputs and outputs, we recommend using

the RS485 interface, which is available or optional in

most of our products.

INSTALATION

The controller was designed to be fixed by screws, behind a face of

metal panels of equipment or machinery. Display and keyboard

should fit in appropriate cut of this panel. The following figures show

the dimensions and distances required for attachment.