beautypg.com

NOVUS RHT-Air User Manual

Rht-air, 1 introduction, 2 specifications

background image

NOVUS AUTOMATION

1/8

RHT-Air

WIRELESS EQUIPMENT FOR TEMPERATURE AND HUMIDITY – INSTRUCTIONS MANUAL V1.0x A

1 INTRODUCTION

RHT-Air comes with a high precision and stability sensor to measure both

temperature and relative humidity. Because it operates with a

microprocessor, it can be fully configured through its USB and IEEE 802.15.4

interfaces, using Modbus RTU commands. The software DigiConfig enables

for all the equipment’s resources to be configured.
RHT-Air can be configured to display the temperature and Relative Humidity

measured or even, the temperature and the Dew Point
RHT-Air should be connected (via wireless) to an AirGate-Modbus so that

its registers can be read whenever it is in operation.

1.1 IDENTIFICATION
The following elements appear in the front part of the equipment:

Fig. 1RHT-Air main screen

Communication Indicator (COM): It signals that the device is receiving data

from the Modbus network.

Button (Programming): This button is used to configure the Modbus

address, the Update Interval and screen changes.
Temperature: Room temperature measured by the equipment.
Relative Humidity: Relative Humidity measurement.

Fig. 2RHT-Air’s second screen

Communication Address: Programmed value to identify the Modbus

network equipment. Programmable between 1 and 246.






2 SPECIFICATIONS

Equipment’s operating

temperature

RTH-Air = from -10 °C to 70 °C

Electromagnetic

compatibility

EMC: EN61326-1:2006 CISPR11/EN55011,

EN61000-4-2, EN61000-4-3, EN61000-4-4,

EN61000-4-6, EN61000-4-8

Sensor’s measurement

range

Temperature: -40.0 °C to 100.0 °C.
Relative Humidity (RH): 0.0 to 100.0 % RH.

(No Condensation)

Dew point: -40.0 °C and 100.0 °C

Precision of

measurements

See Fig. 3.
Note: measurement errors can be discarded

through the software’s OFFSET parameter.

Resolution of

measurements:

Temperature: 0.1 °C. 14 bits (16383 levels)
Relative Humidity (RH): 0.1 %. 12 bits (4095

levels)

Response time

(Sensor)

Temperature: Up to 30 s in slow moving air.
Humidity: Up to 8 s in softly moving air (20 to

80 % RH).

Interval between updates A minimum of 15 seconds. No more than 30

minutes (1800 s)

Power supply

12 Vdc to 30 Vdc, consumption < 100 mA or

Lithium battery of 3.6 Vcc (1/2 AA), internal.

Connections

Internal USB Device (Mini-B) for

configuration and firmware update.

• Groove RP SMA (Plug) connector for

antenna.

• Power supply connector.

Wireless

• Maximum transmission power of 25,11

mW (14 dBm).

• Maximum Range: 500 meters line-of-sight

in open field.

• Receptor sensibility - 92 dBm.
• Operation band ISM 2.4 GHz.
• DSSS Technology - Direct Sequence

Spread Spectrum.

• OQPSK Modulation - Offset Quadrature

Phase Shift Keying.

• 15 operation channels.
• AES-CBC-128 (Advanced Encryption

Standard).

Storage

Polycarbonate

Level of protection

The product is suitable for applications that

require a level of protection of up to IP65.
Electronic module box: IP65; Sensor capsule:

IP40.

Dimensions

60 x 70 x 35 mm + antenna 105 mm + sensor

37.2 mm

Weight

171 grams / 40 grams (cable)

DigiConfig software

configuration environment

Configuration Software Windows®.
Menus in Portuguese, English or Spanish.
It configures, reads and displays data on the

screen.

Certifications

CE, ANATEL (0172-13-7089)