beautypg.com

NOVUS Controller N1200 User Manual

Controller n1200

background image

NOVUS AUTOMATION

1 / 13

Controller N1200

UNIVERSAL CONTROLLER - INSTRUCTIONS MANUAL – V2.0x

SAFETY ALERTS

The symbols below are used on the equipment and throughout this

document to draw the user’s attention to important operational and

safety information.

CAUTION:

Read the manual thoroughly

before installing and operating the

equipment.

CAUTION OR DANGER:

Electrical Shock Hazard

All safety related instructions that appear in the manual must be

observed to ensure personal safety and to prevent damage to either

the instrument or the system. If the instrument is used in a manner

not specified by the manufacturer, the protection provided by the

equipment may be impaired.

INTRODUCTION

The N1200 is an extraordinarily versatile process controller. It holds

in one single instrument all the main features needed for the vast

majority of industrial processes. It accepts in a single model virtually

all the sensors and signals used in the industry and provides the

main output types required for the operation of diverse processes.
The configuration can be performed directly on the controller or

through the USB interface. The NConfig software (free) is the

configuration management tool. Connected to the USB of a Windows

computer, the controller is recognized as a serial communications

port (COM) running with a Modbus RTU protocol.
Through the USB interface, even if disconnected from the power

supply, the configuration performed in a piece of equipment can be

can be saved in a file and repeated in other pieces of equipment that

require the same configuration.
It is important that the users read carefully this manual before using

the controller. Verify if the release of this manual matches the

instrument version (the firmware version is shown when the controller

is energized). The N1200 main characteristics are:
• Multi-sensor universal input;
• Protection for open sensor in any condition;
• Relay, 4-20 mA and logic pulse control outputs all available in

the standard model;

• Self-tuning of PID parameters;
• Automatic / Manual function with “bumpless” transfer;
• Four modes of independents alarms, with functions of minimum,

maximum, differential (deviation), open sensor and event;

• Timer functions that can be associated to the alarms;
• Retransmission of PV or SP in 0-20 mA or 4-20 mA;
• Input for remote setpoint;
• Digital input with 5 functions;
• Programmable soft-start;
• 20 setpoint profile programs with 9 segments each, with the

ability to be linked together for a total of 180 segments;

• Password for parameters protection;
• Universal power supply.

CONFIGURATION / FEATURES

INPUT TYPE SELECTION
Select the input type (in parameter “tYPE”) from Table 1 below.

TYPE

CODE

RANGE OF MEASUREMENT

J

Tc j

Range: -110 to 950 ºC (-166 to 1742 ºF)

K

Tc k

Range: -150 to 1370 ºC (-238 to 2498 ºF)

T

Tc t

Range: -160 to 400 ºC (-256 to 752 ºF)

N

Tc n

Range: -270 to 1300 ºC (-454 to 2372 ºF)

R

Tc r

Range: -50 to 1760 ºC (-58 to 3200 ºF)

S

Tc s

Range: -50 to 1760 ºC (-58 to 3200 ºF)

B

Tc b

Range: 400 to 1800 ºC (752 to 3272 ºF)

E

Tc e

Range: -90 to 730 ºC (-130 to 1346 ºF)

Pt100

Pt

Range: -200 to 850 ºC (-328 to 1562 ºF)

0-20 mA

L0.20

Linear Signals

Programmable indication from -1999 to 9999.

4-20 mA

L4.20

0–50 mV

L0.50

0-5 Vdc

L0.5

0-10 Vdc

L0.10

4-20 mA

NON

LINEAR

ln j

Non Linear Analog Signals

Indication range depends on the selected sensor

Ln k

ln t
ln n
ln r
ln s
ln b
ln E
Ln.Pt

Table 1 - Input types

Note: All input types are factory calibrated.
CONFIGURATION OF OUTPUTS, ALARMS AND DIGITAL INPUTS
The controller input and output channels (I / O) can assume multiple

functions: control output, digital input, digital output, alarm output,

retransmission of PV and SP. These channels are identified as I / O

1, I / O 2, I / O 3, I / O 4 and I / O 5.
The basic controller model comes loaded with the following features:

I / O 1- output to Relay SPST-NA;

I / O 2- output to Relay SPST-NA;

I / O 5- current output, digital output, digital input;

Optionally, other features can be added, as shown under the item

“Identification” in this manual:

- 3R: I / O3 with output to SPDT relay;
- DIO: I / O3 and I / O4 as digital input and output channels;
- HBD: Heater break detect;
- 485: Serial Communication;

The function to be used in each channel of I/O is defined by the user

in accordance with the options shown in the Table 2.