beautypg.com

NOVUS N1020 User Manual

N1020

background image

N1020

Communication Protocol V10x A

1. SERIAL COMMUNICATION

1.1 COMMUNICATION INTERFACE

The optional serial interface RS485 allows to address up to 247 controllers in a network

communicating remotely with a host computer or master controller.
RS485 Interface
• Compatible line signals with RS485 standard;
• 3 wire connection from master to up to 31 slaves indicators in a multidrop bus. It is

possible address 247 nodes with multiple outputs converters;

• Maximum communication distance: 1000 meters.
• The RS485 signal are:

D1 = D:

Bidirectional data line.

D0 = D:

Bidirectional inverted data line.

C = GND:

Optional connection which left communication better.

General Characteristics
• Optically isolated serial interface;
• Programmable baud rate: 1200, 2400, 4800, 9600, 19200, 38400, 57600 and

115200 bps.

• Data Bits: 8
• Parity: None, Even or Odd.
• Stop Bits: 1

1.2 CONNECTIONS

Communication Protocol
The MOSBUS RTU slave is implemented, available in most SCADA softwares in the

market.
All configurable parameters can be accessed (for reading or writing) through the

Registers Table. Broadcast commands are supported as well (address 0).
The available Modbus commands are:

03 - Read Holding Register;
05 - Force Single Coil (Force Digital Output State);
06 - Preset Single Register;
16 - Preset Multiple Register.

The registers are arranged in a table in such a way that several registers can be read in

the same request.

1.3 CONFIGURATION OF SERIAL COMMUNICATION PARAMETERS

Three parameters must be configured in the device for serial communication:

bavd

: Baud rate. All devices with same baud rate.

addr

: Device communication address. Each device must have an exclusive

address.

Prty

: Parity.

1.4 REGISTERS TABLE

Equivalent to the registers referenced as 4X.
The holding registers are basically a list of the internal indicator parameters. All

registers above address 12 can be read or written. The registers up to this address in

more are read only. Please verify each case. Each table parameter is a 16 bits two

complement signed word.

Holding

Registers Parameter

Register Description

0000

Active SP

Read: Active control SP (main SP, from ramp and

soak or from remote SP).

Write: to main SP.

Range: from spll to spkl.

0001

PV

Read: Process Variable.

Write: Not allowed.

Range: Minimum value is the one configured in spll

and the maximum value is the one configured in
spkl

. Decimal point position depends on dppo

value.

In case of temperature reading, the value read is

always multiplied by 10, independently of dppo

value.

0002

MV

Read: Output Power in automatic or manual mode.

Write: Not allowed. See address 28.

Range: 0 to 1000 (0.0 to 100.0 %).

0003

Reserved

0004

Display value

Read: Current value shown on display.

Write: Current value shown on display.

Range: -1999 to 9999. The range depends on the

displayed parameter.

0005

Prompt index

Read: Current prompt position in the parameters

flowchart.

Write: not allowed. Range: 0000h to 060Ch

Prompt number format: XXYYh, where:

XX→ menu cycle number

YY→ prompt number (index).

0006

Status Word 1 Read: Status bits. See table 2.

Write: not allowed.

0007

Software

Version

Read: The firmware version of controller. If V1.00, the

read value will be 100.

Write: not allowed.

0008

ID

Read: controller identification number: 65

Write: not allowed.

0009

Status Word 2 Read: Status bits. See table 2.

Write: not allowed.

0010

Status Word 3 Read: Status bits. See table 2.

Write: not allowed.

0011

Ir

Integral Rate (in repetitions/min)

Range: 0 to 9999 (0.00 to 99.99)

0012

dt

Derivative Time (in seconds).

Range: 0 to 3000 (0.0 to 300.0)

0013

pb

Proportional Band (in percentage)

Range: 0 to 5000 (0.0 to 500.0)

0014

Reserved

0015

ct

Cycle Time (PWM, in seconds)

Range: 5 to 1000 (0.5 to 100.0)

0016

Freq

Read/Write: Mains frequency.

Range: 0 – 1 (60/50Hz)

0017

Kyst

On/Off Control Hysteresis (in selected type

engineering unit).

Range: 0 to spkl - spll

0018

fltr

Read/Write: PV digital filter gain.

Range: 0 – 20

0019

Ovll

Output Low Limit (minimum output power)

Range: 0 to 1000 (0.0 to 100.0 %).

0020

ovkl

Output High Limit (minimum output power)

Range: 0 to 1000 (0.0 to 100.0 %).

0021~0022 Reserved

0023

Serial Number

High

Write: Not allowed.

First four digits of Serial Number.

Range: 0 to 9999. Read only

0024

Serial Number

Low

Write: No allowed.

Last four digits of Serial Number.

Range: 0 to 9999. Read only

0025

SP

Control Setpoint (Prompt Setpoint).

Range: from spll to spkl.

0026

spll

Setpoint Low limit.

Range: minimum value depends on the input type

selected in type (see Table 1) to spkl.

0027

Spkl

Setpoint High limit.

Range: minimum value is spll and maximum

depends on the input type selected in type (see

Table 1).

0028

Reserved

Internal use.

0029

offs

PV offset

Range: from spll to spkl