NOVUS Controller N3000 User Manual

Controller n3000, Presentation, Configuration

background image

NOVUS AUTOMATION

1/11

Controller N3000

UNIVERSAL PROCESS CONTROLLER – INSTRUCTIONS MANUAL – V3.0x

SAFETY ALERTS

The symbols below are used on the equipment and throughout this

document to draw the user’s attention to important operational and

safety information.

CAUTION or WARNING:

Read complete instructions prior to

installation and operation of the unit.

CAUTION or WARNING:

Electrical Shock Hazard

All safety related instructions that appear in the manual must be

observed to ensure personal safety and to prevent damage to either

the instrument or the system. If the instrument is used in a manner

not specified by the manufacturer, the protection provided by the

equipment may be impaired.

PRESENTATION

The N1100 is an extraordinarily versatile process controller. It holds in

one single instrument all the main features needed for the vast majority

of industrial processes. It accepts in a single model virtually all the

sensors and signals used in the industry and provides the main

output types required for the operation of diverse processes.
The configuration can be performed directly on the controller or through

the USB interface. The NConfig software (free) is the configuration

management tool. Connected to the USB of a Windows computer, the

controller is recognized as a serial communications port (COM) running

with a Modbus RTU protocol.
Through the USB interface, even if disconnected from the power supply,

the configuration performed in a piece of equipment can be can be

saved in a file and repeated in other pieces of equipment that require

the same configuration.
It is important that the users read carefully this manual before using

the controller. Verify if the release of this manual matches the

instrument version (the firmware version is shown when the controller

is energized).
• Multi-sensor universal input (sensors and standard signals);
• Relay, 4-20 mA and logic pulse control outputs all available in the

standard model;

• Self-tuning of PID parameters;
• Automatic / Manual function with “bumpless” transfer;
• Four modes of independents alarms, with functions of minimum,

maximum, differential (deviation), open sensor and event;

• Timer functions that can be associated to the alarms;
• Retransmission of PV or SP in 0-20 mA or 4-20 mA;
• Input for remote setpoint;
• Digital input with 5 functions;
• Programmable soft-start;
• 7 setpoint profile programs with 7 segments each, with the ability

to be linked together for a total of 49 segments;

• Comunicação serial RS-485, protocolo MODBUS RTU;
• Password for parameters protection;
• Universal power supply.

CONFIGURATION

INPUT TYPE SELECTION
Select the input type (in parameter “tYPE”) from Table 1 below.

TYPE

CODE

CHARACTERISTICS

J

Tc j

Range: -110 a 950 ºC (-166 a 1742 ºF)

K

Tc k

Range: -150 a 1370 ºC (-238 a 2498 ºF)

T

Tc t

Range: -160 a 400 ºC (-256 a 752 ºF)

N

Tc n

Range: -270 a 1300 ºC (-454 a 2372 ºF)

R

Tc r

Range: -50 a 1760 ºC (-58 a 3200 ºF)

S

Tc s

Range: -50 a 1760 ºC (-58 a 3200 ºF)

B

Tc b

Range: 400 a 1800 ºC (752 a 3272 ºF)

E

Tc e

Range: -90 a 730 ºC (-130 a 1346 ºF)

Pt100

Pt

Range: -200 a 850 ºC (-328 a 1562 ºF)

0–50 mV

L.0.50

Linear Signals

Programmable indication from-1999 to 9999

4-20 mA

L.4.20

0-5 Vdc

L0.5

0-10 Vdc

L0.10

4-20 mA

Sqrt

4-20 mA input with Square Root extraction.

Programmable indication from-1999 to 9999

4-20 mA

NO

LINEAR

ln j

Non Linear Analog Signals

Indication range depends on the selected sensor

Ln k

ln t

ln n

ln r

ln s

ln b

ln E

Ln.Pt

Table 1 - Input types

Note: All input types are factory calibrated.

OUTPUTS, ALARMS AND DIGITAL INPUTS CONFIGURATION
The controller input/output channels can assume multiple functions,

depending on configuration: control output, alarm output, digital

output, digital input, and PV or SV analog retransmission. These

channels are identified as I/O1, I/O2, I/O3, I/O4, I/O 5 and I/O6.
The basic controller model comes loaded with:
I/O1 and I/O2 - SPDT relay output;

I/O3 and I/O4 - SPST relay output;

I/O5 - analog output (0-20 or 4-20 mA), pulse 10 V max, digital I/O;

I/O6 - Digital Input.
Note: When a function is selected to operate through digital

input, the controller does not respond to the equivalent function

command given in the frontal keypad.