NOVUS Controller N120 User Manual
Controller n120, Introduction, Características principais
Controller N120
INSTRUCTIONS MANUAL – V2.0x
INTRODUCTION
N120 has all the main features needed for control and alarm functions in
different industrial processes. It accepts in a single model the majority
of the sensors and signals used in the industry and provides the main
output types required for dual action control (Heat and Cool) and
alarm monitoring.
The configuration can be performed directly on the controller or
through the USB interface. The NConfig software (free) is the
configuration management tool. Connected to the USB of a Windows
computer, the controller is recognized as a serial communications
port (COM) running with a Modbus RTU protocol.
Through the USB interface, even if disconnected from the power
supply, the configuration performed in a piece of equipment can be
can be saved in a file and repeated in other pieces of equipment that
require the same configuration.
The N120 in addition to being a controller is an electronic datalogger.
The logger function operates independently of the controller. The
parameter setting of the datalogger is made using LogChart-II
software.
It is important that the users read carefully this manual before using
the controller. Verify if the release of this manual matches the
instrument version (the firmware version is shown when the controller
is energized).
CARACTERÍSTICAS PRINCIPAIS
• Capable of storing 32700 registers (datalogger);
• Universal multi-sensor input without hardware change;
• Protection for open sensor in any condition;
• Relay and logic pulse control outputs available in the standard
model;
• Self-tuning of PID parameters;
• Automatic / Manual function with “bumpless” transfer;
• Up to 4 alarm outputs, with functions of minimum, maximum,
differential (deviation), open sensor and event;
• Timer functions that can be associated to the alarms;
• Digital input with 4 functions;
• Programmable soft-start;
• 20 setpoint profile programs with 9 segments each, with the ability
to be linked together for a total of 180 segments;
• Password for parameters protection;
• Função LBD (loop break detector);
• Universal power supply: 100-240 Vac, ±10 %.
OPERATION
The controller front panel is shown in Fig. 1.
Fig. 1 – Front panel elements
Display: Shows the value and status of the controller parameters.
COM indicator: Flashes to indicate communication activity in the
RS485 interface.
TUNE indicator: Stays ON while the controller is in tuning process.
MAN indicator: Signals that the controller is in the manual control
mode.
RUN indicator: Indicates that the controller is active, with the control
output and alarms enabled.
OUT indicator: For relay or pulse control output; it reflects the actual
state of the output. If an analog output is assigned for control, the
OUT indicator lights continuously.
A1, A2, A3 and A4 indicators: signalize the occurrence of alarm
situation.
P
P Key (Program key): used to walk through the menu
parameters.
B
Back Key: used to retrocede parameters.
Increment key and
- Decrement key: allow altering the
values of the parameters.
When the controller is turned on, its firmware version is delayed for 3
seconds, after which the controller starts normal operation. The
values of PV and SP are displayed and the outputs are enabled.
In order to operate appropriately, the controller needs a configuration
that is the definition of each one of the several parameters presented by
the controller. The user must be aware of the importance of each
parameter and for each one determine a valid condition or a valid value.
Important:
Always the first parameter to set is the input type.
The parameters are grouped in levels according to their functionality
and operation easiness. The 7 levels of parameters are:
LEVEL
ACCESS
1 - Operation
Free access
2 - Tuning
Reserved access
3- R&S Programs
4- Alarms
5- Scale
6- Outputs
7- Calibration
Table 1 – Cycles of Parameters
Document Outline
- Controller N120
- INSTRUCTIONS MANUAL – V2.0x
- introduction
- CARACTERÍSTICAS PRINCIPAIS
- operation
- ConfiguraTION / FEATURES
- instalation
- description of the parameters
- PROTECTION OF CONFIGURATION
- PROGRAMs OF RAMP AND soak
- DETERMINATION OF PID PARAMETERS
- specifications
- MAINTENANCE
- warranty
- APPENDIX 1 - SOFTWARE LOGCHART-II
- Anexo 2 –SERIAL communication