beautypg.com

Anexo 2 –serial communication, Characteristics, Communication protocol – NOVUS Controller N120 User Manual

Page 14: Holding registers table

background image

NOVUS AUTOMATION

14/14

ANEXO 2 –SERIAL COMMUNICATION

The controller can be supplied with an asynchronous RS-485 digital

communication interface for master-slave connection to a host

computer (master). The controller works as a slave only and all

commands are started by the computer which sends a request to the

slave address. The addressed unit sends back the requested reply.

Broadcast commands (addressed to all indicator units in a multidrop

network) are accepted but no reply is sent back in this case.

CHARACTERISTICS
• Signals compatible with RS-485 standard. MODBUS (RTU)

Protocol. Two wire connection between 1 master and up to 31

(addressing up to 247 possible) instruments in bus topology. The

communication signals are electrically insulated from the rest of the

device;

• Maximum connection distance: 1000 meters.
• Time of disconnection for the controller: Maximum 2 ms after last

byte.

• Selectable speed; 8 data bits; 1 stop bit; selectable parity (no parity,

pair or odd);

• Time at the beginning of response transmission: maximum 100 ms

after receiving the command.

The RS-485 signals are:

D1 D D + B Bi-directional data line.

Terminal 16

D0

D:

D - A Bi-directional inverted data line.

Terminal 17

C

Optional connection that

improves the performance of the

communication.

Terminal

18

GND

CONFIGURATION OF PARAMETERS

FOR SERIAL

COMMUNICATION
Two parameters must be configured for using the serial type:
bavd

: Communication speed.

prty

: Parity of the communication.

addr

: Communication address for the controller.

REDUCED REGISTERS TABLE FOR SERIAL

COMMUNICATION

COMMUNICATION PROTOCOL
The MOSBUS RTU slave is implemented. All configurable

parameters can be accessed for reading or writing through the

communication port. Broadcast commands are supported as well

(address 0).
The available Modbus commands are:

03 - Read Holding Register

06 - Preset Single Register

05 - Force Single Coil

16 - Preset Multiple Register

HOLDING REGISTERS TABLE
Follows a description of the usual communication registers. For full

documentation download the Registers Table for Serial

Communication in the N120 section of our web site.

Address Parameter

Register Description

0000

Active SP Read: Active control SP (main SP, from

ramp and soak or from remote SP).
Write: to main SP.
Range: from spll to spkl.

0001

PV

Read: Process Variable.
Write: Not allowed.
Range: Minimum value is the one

configured in spll and the maximum

value is the one configured in spkl.

Decimal point position depends on dppo

value.
In case of temperature reading, the value

read is always multiplied by 10,

independently of dppo value.

0002

MV

Read: Output Power in automatic or

manual mode.
Write: Not allowed. See address 28.
Range: 0 to 1000 (0.0 to 100.0 %).