beautypg.com

NOVUS TxIsoLoop-1/TxIsoLoop-2 User Manual

Txisoloop-1 / txisoloop-2

background image

NOVUS AUTOMATION

1/2

TxIsoLoop-1 / TxIsoLoop-2

LOOP-POWERED ISOLATORS - OPERATING MANUAL V1.0x D

INTRODUCTION

The TxIsoLoop-1 and TxIsoLoop-2 are 0(4)-20 mA signal isolators

with one and two channels respectively. They provide signal

protection by electrically isolating the input signal from the output.

The 4-20 mA input is measured and an identical isolated signal is

produced at the output. Its power is obtained from the 0(4)-20 mA

input loop, dropping the need for an external power supply.

CHARACTERISTICS

• Input/output galvanic isolation.
• Models for 1 or 2 channels.
• Don’t require power supply.
• High accuracy.
• Calibration free.

ESPECIFICAÇÕES

• Input Signal (INPUT): 0 to 20 mA; 4 to 20 mA

(check minimum current for proper operation)
• Max. Input voltage (Vin max.): 32 Vdc
• Voltage drop input/output without protection (Vdrop): < 3 Vdc
• Voltage drop input/output with protection (Vdrop): < 5 Vdc
• Output Signal (OUTPUT): 0(4) to 20 mA
• Max. Load (RL): 1450 R
• Accuracy: 0.2 % FS @ 0 a 60 ºC / RL= 250 R

0.3 % FS @ -20 a 75 ºC / RL= 250 R
• Operating current: > 0,1 mA
• Overload: < 40 mA; < 32 Vdc
• Response time: 2 ms @ RL= 250 R
• Isolation: 3000 Vac / 10 s

240 Vac continuous
• EMC: EN 61326-1
• Ambient temperature range: -20 to + 75 ºC
• Humidity: 20 a 90 %
• Case: ABS (60 %) + PC (40 %). Protection: IP40
• Wire gauge for connections: 0.14 a 1.5 mm²
• Recommended torque: 0.8 Nm
• Terminal blocks injected in Polyamide.

ELECTRICAL INSTALLATION

For proper operation, the TxIsoLoop requires some minimum

voltage in the input loop. This voltage can be found in two ways:
1. In type source devices (transmitters, controllers, etc), this voltage

is provided by the device itself.

Fig. 1 – TxIsoLoop typical connections

The minimum operating voltage can be calculated by the equation

below:

V1 = Vin

Where: Vin = Vdrop + ( Iout(máx) x RL )

Iin = Iout

2. In sink type devices (2-wire transmitters) the energy is provided by

an external power supply in series in the loop, as shown in Fig. 2.

Fig. 2 – TxIsoLoop used to isolate a 2-wire transmitter

In this arrangement, the power supply must provide enough voltage

such as power both the 2-wire transmitter and the TxIsoLoop.
The minimum voltage required to allow proper operation can be

obtained from the equation below:

V1 = Vb +
Vin

Where: V1= Power supply voltage

Vb= Voltage required by the 2-wire

transmitter

Vin = Vdrop + ( Iout(máx) x RL )

Iin = Iout