Nor-Lake Refrigeration Systems User Manual
Page 3
09/14 Rev. E 101628
3
UNIT COOLERS
UL LISTED
Forced air type with low profile design
Designed for ceiling installation with air discharge parallel to the walk-in ceiling
Fan motors, guards, and multi fin or tube type direct expansion coil are enclosed in a heavy
gauge aluminum housing
Include drain pan with suitable drain pipe connection
Freezer models have an automatic electric defrost system including heaters, time clock, defrost
termination and fan delay control, heated drain pan, and heater limit switch
Defrosts are time initiated and temperature terminated with a built in fail safe control
REFRIGERANT
R404A for high/medium temperature applications.
NOTE
: R404A system’s compressors use POE oils. DO NOT leave the compressor service
valves open for over five minutes, as this will contaminate the oil with moisture and void the
warranty.
ELECTRICAL
No inter-wiring required between the evaporator and condensing unit
Two point electrical connection, one at the condensing unit and one at the unit cooler, provided
for field hook up
Rack mounted control box that encloses factory pre-wired pressure controls and contactor for
three phase units
NOTE: Nor-Lake wiring diagram is provided. Keep for reference. DO NOT use any other
diagram
PROVIDED EQUIPMENT FOR FIELD INSTALLATION
Liquid line filter drier
Sight glass
Solenoid valve
Room temperature control
Expansion valve
Evaporator mounting kit
Defrost time clock
FIELD INSTALLATION REQUIREMENTS
Refrigerant piping
Evaporator drain line
Freezer drain line heater
OPTIONAL FEATURES
Pre-charged systems, up to 3 horsepower, with line sets up to 50 feet long using reusable quick
connect refrigerant line fittings
Pre-piped with the liquid line filter drier, sight glass, and hand valve factory installed (not
applicable to pre-charged systems)
Pre-wired to allow for a single point electrical connection at the condensing unit (will require field
inter-wiring between the evaporator and condensing unit)
NOTE: Nor-
Lake will custom design and build refrigeration systems to meet the customer’s needs
.