beautypg.com

Specifications, 150kw infrastruxure pdu, 150kw infrastruxure pdu – American Power Conversion PD150G6F User Manual

Page 73

background image

150kW InfraStruXure PDU—Operation and Configuration

65

Specifications

150kW InfraStruXure PDU

Electrical PD150G6F

PD150L6F

Input

Nominal voltage

480V, 3-phase

600V, 3-phase

Voltage AC

3-phase, 3-wire 3-phase,

3-wire

Frequency

60Hz , ±3Hz

60Hz, ±3Hz

Max. current per phase

200A

150A

Load capacity

150,000VA

150,000VA

Max. crest factor

3

3

Output

Nominal voltage

120, 208V 1-phase and 208V 3-phase

Full load rating

150kVA

Nominal current

416A

Distribution breaker size

225A (maximum size)

Main panel breaker

400A MCCB

Subfeed breaker

150A/225A

Relay Outputs

Nominal switching capacity

1A at 30VDC

Maximum switching power

30W

Maximum switching voltage

60VDC

Maximum switching currant

2ADC

Maximum carrying current

2ADC

Surge ratings

2kV per Bellcore TA-NWT-001089
1.5kV per FCC part 68

Physical PD150G6F

PD150L6F

Dimensions (H × W × D)

PDU

81 Ч 29 Ч 36in (2060 Ч 740 Ч 910mm)

Shipping

86 Ч 36 Ч 48in (2180 Ч 910 Ч 1220mm)

Weight

PDU only

1500lb (680kg)

1400lb (635kg)

PDU with 28 cables

1900lb (862kg)

1800lb (816kg)

Shipping

1950lb (885kg)

1850lb (839kg)