PDU Display Interface: Contacts Screen

20

150kW InfraStruXure PDU—Operation and Configuration

How to connect contacts to the PDU monitoring unit.

1. Choose one or more contact number (s) on the User/EPO contacts port on the user connection

plate to which you will connect the contacts. The user connection plate connects to the PDU
monitoring unit.

2. From the PDU display interface:

a. Press the

E

SC

or

E

NTER

key to go to the top-level menu screen.

b. Select Contacts on the top-level menu screen, and press the

E

NTER

key.

c. Select Contact Inputs and press

E

NTER

to display the contact inputs screen.

d. Select Contact In and press the

E

NTER

key to select the number of the contact you are

connecting. The continue arrow will appear next to the contact number.

e. Press the Up or Down arrow key to select the appropriate contact number, and press the

E

NTER

key.

f. Press the Down arrow key to enter a unique Name for the contact and to configure the

Normal state of the contact (Open or Closed). The default Normal state is Open. Press the

E

NTER

key to select the item to configure.

3. Connect contact wires (300V-rated cabling required) to the User Contacts terminal block on

the user connection plate. You will need a 2.5-mm standard screwdriver.

4. Run the wires from the terminal block out the roof or under the floor of the PDU to your

contact’s location.

Note

You will be prompted for your password to configure these items.

Warning

Ensure that wires are properly retained and away from high voltage lines and
breakers.

Load-Meter
Volt-Meter
Contacts
Breakers

Alarms
Panel
Config
Help

>Contact Inputs
>Relay Outputs
>Alarm Relay Map

Contact In:01of04
Name: User Contact1
Normal:Open
Status: Closed