Rear view (interior)

 The PDU monitoring unit receives signals from several current and voltage

monitoring boards that report to a central board assembly located in the PDU
monitoring unit. The monitoring unit has one 10 Base-T (Cat-5) connection to the
Information Controller Hub (or switch), four relay output connections, four input
contact connections, and one EPO input connection. Make these connections at the
user connection plate located on the roof of the PDU. See “PDU monitoring unit”
on page 10
for a more detailed description.

 The Main Input breaker connects to your main power source. The breaker accepts

480V input and requires 3-wire input conductors.