16

150kW InfraStruXure PDU—Operation and Configuration

Load-Meter Screen

From the Load-Meter screen, you can select the following items:

Total Load by Phase

The load supported by each phase in kilovolt-amperes (kVA), in
RMS current (Irms), and as a percentage of the maximum allowable
load (%LD).

Total Load Summary For the total load supported:

kW: The power provided, in kilowatts.
kVA: The actual power drawn by the load, in kilovolt-amperes.
Freq: The frequency.
PF: The power factor, which affects the power available to the

load.

%LD: The load as a percentage of the maximum allowable

load.

Power Factor

For each phase:

kVA: The actual power drawn by the load, in kilovolt-amperes.
kW: The power, in kilowatts, provided by the phase.
PF: The power factor (kW/kVA) that affects the power

available to the load.