How to download firmware updates – American Power Conversion PD150G6F User Manual
Page 71

150kW InfraStruXure PDU—Operation and Configuration
63
How to Download Firmware Updates
From a local computer
1. Select a serial port at the local computer, and disable any service that uses that port.
2. Use the configuration cable to connect the selected port to the console port on the PDU
monitoring unit.
3. Run a terminal program (such as HyperTerminal
®
) and configure the selected port for 9600 bps,
8 data bits, no parity, 1 stop bit, and no flow control. Save the changes.
4. Press
E
NTER
twice to display the User Name prompt.
5. Enter your User Name and Password (both apc, for administrators only) and press the
E
NTER
key.
6. From the Control Console menu, select System, then Tools, then File Transfer, then
XMODEM.
7. The system will prompt you with Perform transfer with XMODEM –CRC? Type Yes
and press
E
NTER
.
8. The system will then prompt you to choose a transfer rate and to change your terminal settings
to match the transfer rate. Press
E
NTER
to set the PDU to accept the download.
9. In the terminal program, send the file using XMODEM protocol. Upon completion of the
transfer, the console will prompt you to restore the baud rate to normal.
The PDU network management interface will reboot when the download is complete.
See also
To download a firmware upgrade and transfer it to your PDU, see “File Transfers” in the
InfraStruXure PDU’s online Network Management User’s Guide on the Utility CD.
Caution
Do not interrupt the download.