Customizing and Updating the PDU

60

150kW InfraStruXure PDU—Operation and Configuration

Connect an EPO switch to the user connection plate and test the switch

1. Connect the switch to the EPO connection point terminals located on the bottom side of the

PDU user connection plate. Read the label next to the terminal block to determine which
terminals to connect to for the signal type you are using:
– Contact Closure—Normally Open

– Contact Closure—Normally Closed

– 24VAC/VDC—Normally Open

2. Verify that the EPO DIP switches on the PDU monitoring unit are configured properly for the

signal type you are using. The labels above the switches and the figure below show the correct
settings for both the Normally Open (NO) and Normally Closed (NC) position.

Note

The default setting on the EPO interface on the PDU monitoring unit is for a Normally
Open (NO)
switch.

1

2

3

4

AT

S

E

N

ATS

0

AT

S

1

ATS

2

EPO

Contact

– +

EPO 24V

AC/DC

Contact Inputs

Contact Outputs

USER INTERFACE

© 2001 APC

MADE IN USA

External set of

Normally Open Dry Contacts

1

2

3

4

AT

S

E

N

ATS

0

AT

S

1

ATS

2

EPO

Contact

– +

EPO 24V

AC/DC

Contact Inputs

Contact Outputs

USER INTERFACE

© 2001 APC

MADE IN USA

External set of

Normally Closed Dry Contacts

1

2

3

4

AT

S

E

N

ATS

0

AT

S

1

ATS

2

EPO

Contact

– +

EPO 24V

AC/DC

Contact Inputs

Contact Outputs

USER INTERFACE

© 2001 APC

MADE IN USA

24V AC or DC Power Supply

External set of

Normally Open Dry Contacts

NO

NC

TRIPPED

ARMED

TEST

EP

O

Norma

lly Closed

Normally Open or 24V

AC/DC

Location of switches

on PDU monitoring unit