beautypg.com

Electrical config, Manufacturer data – American Power Conversion PD150G6F User Manual

Page 37

background image

PDU Display Interface: Config Screen

150kW InfraStruXure PDU—Operation and Configuration

29

Electrical Config

This option of the Config screen displays information about the electrical service that provides input
to the InfraStruXure PDU. All of the values displayed on this screen are set at the factory. Use this
information when viewing and setting alarms.

Manufacturer Data

Use this option of the Config screen to display a scrollable list containing information about the
InfraStruXure PDU. This information is useful when requesting service or product updates. The
following information is displayed:

• Manufacturer Name
• Date of Manufacture
• Date of Calibration
• Hardware Revision
• Firmware Revision (for PDU Monitoring and Metering)
• Serial Number
• Model Number

Input Config

Configure the following items:

Main Input: The voltage from the power source coming into

the PDU main input switch.

• 3W: 3-phase Delta, measured line-to-line
• 4W: 3-phase WYE, measured line-to-neutral

Transformer: Indicates whether the InfraStruXure PDU has

a transformer.

Output Config

Configure the following items:

Panel Voltage: The nominal voltage of the distribution panels

supplying power to the load equipment. (This is measured
line-to-neutral.)

Panel Breaker: The rating, in amps, of the circuit breaker

feeding the distribution panels.