American Power Conversion PD150G6F User Manual
Page 27
PDU Display Interface: Contacts Screen
150kW InfraStruXure PDU—Operation and Configuration
19
Alarm Relay Map
Configure the relay outputs, using
the Alarm Relay Map. Each
Alarm Map corresponds to a relay
output. For example, Alarm Map
01of04 corresponds to the first of four relay outputs. The second line,
in brackets [ ], lists the items that you have selected to map to the
selected relay. The third line allows you to select the alarms to which
you want to map the relay:
• Any Load (L)—Maps to over- or under-current alarms for
circuit breaker panels and branch circuits.
• Overload (O)—Maps to over-current alarms for circuit breaker
panels, branch circuits, and SYSGND.
• Input Voltage (Vi)—Maps to any input voltage alarm.
• Output Voltage (Vo)—Maps to any output voltage alarm.
• PDU in Bypass (By)—Not used on this model PDU.
• Any Breaker (Br)—Not used on this PDU.
• Contacts 1–4 (C1,C2,C3,C4)—Maps to the input contact
alarms.
Before exiting the screen, to save your changes, select the Apply
Now option on the bottom line of the screen. You will then be asked
to confirm your changes.
Alarm Map: 01 of 04
[Vo, By, C4]
Map: Input Voltage
Apply Now