Communication Configuration: Configuring the Network Management
150kW InfraStruXure PDU—Operation and Configuration
43
2. Use Ping with a size of 113 bytes to assign the IP address defined by the ARP command. For the
IP address defined in step 1, use one of the following Ping commands:
– Windows command format:
ping 156.205.14.141 -l 113
– LINUX command format:
ping 156.205.14.141 -s 113
3. Use Telnet to access the InfraStruXure PDU at its newly assigned IP address. For example:
telnet 156.205.14.141
4. Use apc for both User Name and Password.
5. See “Control console” on this page to finish the configuration.
Control console
After you log on at the control console, as described in “Local access to the control console” on
page 42 or “Remote access to the control console” on page 42:
1. Choose Network from the Control Console menu.
2. Choose TCP/IP
from the Network menu.
3. If you are not using a BOOTP or DHCP server to configure the
TCP/IP settings, select the Boot Mode menu. Select Manual boot mode, and then press
E
SC
to
return to the TCP/IP menu. (Changes will take effect when you log out.)
4. Set the System
IP
, Subnet Mask, and Default Gateway address values.
5. Press C
TRL
-C to exit to the Control Console menu.
6. Log out (option 4 in the Control Console menu).
Note
If you disconnected a cable during the procedure described in “Local access to the
control console” on page 42, reconnect that cable and restart the associated service.