Overview, Infrastruxure pdu components – American Power Conversion PD150G6F User Manual
Page 13

150kW InfraStruXure PDU—Operation and Configuration
5
Overview
InfraStruXure PDU Components
The APC 150kW InfraStruXure PDU provides distribution and management of electrical power. The
InfraStruXure PDU has the capacity of 150kW, accepts 480V or 600V 3-phase input, and distributes
208V 3-phase power to equipment racks and Rack Distribution Panels (RDPs). The RDPs sit in the
top 10U of specially-designed NetShelter VX enclosures and distributes power to equipment racks.
The InfraStruXure PDU is housed in a specially-designed 23-inch NetShelter VX Enclosure. Each
150kW InfraStruXure PDU has seventy-five (75) pole positions available for feeding equipment
racks and three (3), three-pole positions available for feeding RDPs. Each RDP has thirty-nine (39)
pole positions available for feeding equipment racks and one (1), three-pole position that back-feeds
the RDP.
Rack Distribution Panel (RDP)
75 pole positions available
39 pole positions available
150kW InfraStruXure PDU
One, 3-pole breaker back-feeding the RDP
Three circuit breakers sub-feeding the RDPs
NetShelter VX Enclosure
Power cables feeding equipment racks
42-position circuit breaker panel
Sub-feed power cable feeding the RDP