Customizing and Updating the PDU

150kW InfraStruXure PDU—Operation and Configuration

61

3. Test the EPO switch to ensure that it is wired and working correctly:

a. Place the Arm/Test rocker switch in the Test position. The EPO state LEDs will be off and

the PDU display interface will show the following alarm (in addition to any other active
alarms):

b. Engage the EPO switch. (If your switch is momentary, engage it with one person watching

the EPO state LEDs, and another at the EPO switch.)

c. Observe the EPO LEDs. If the switch is wired and working properly, when the switch is

engaged, both of the EPO state LEDs are red.

d. If the test was successful, place the Arm/Test rocker switch back to the Arm position. The

PDU display interface will clear the EPO test mode alarm. If the test was not successful, see
the troubleshooting chart:

e. Repeat this test for each EPO switch installed.

4. Ensure that the Arm/Test rocker switch is in the Arm position on the monitoring unit.

Problem

Action

Neither state LED was red when
EPO switch was engaged

• Check the wiring to your EPO switch.

• Check to make sure the EPO DIP switch

configuration is correct for your switch
(NO or NC). See step 2 on the previous page for
proper configuration instructions.

Only one of the state LEDs was
red when EPO switch was
engaged

• Check to make sure the EPO DIP switch

configuration is correct for your switch
(NO or NC) and test again. See step 2 on the
previous page for proper configuration
instructions.

• If the switch is configured correctly and both

LEDs are not red after testing again, contact
customer support at a number on the back cover
of this manual.

EPO Ready To Test

Active Alarm xxofxx