PS200/CH200 12 V Charging Regulators
FIGURE 6-2. Battery family dropdown menu
The PS200 is configured at the factory to work with the EnerSys/Genesis 7 Ah
battery algorithm.
For a CH200 change the “Battery Family” to match the battery family being
used. The CH200 is by default sent from the factory with a battery capacity of
zero (0) and a battery family of EnerSys/Genesis NP Series. Setting the battery
capacity at zero (0) forces the charger to only float charge the battery. Battery
capacity must be changed to allow cycle charging and the charging source must
be a DC voltage on the SOLAR and G terminal blocks. TABLE 6-2
shows the
default settings for each of the battery families.