Appendix C. CDM Devices and CPI Bus
Campbell Scientific is introducing the CDM (Campbell Distributed Module) 
line of peripherals, starting with the CDM-VW300 series of vibrating-wire 
analyzers. As multiple CDM devices become available, they will be able to be 
networked to communicate measurement information to a central datalogger. 
The communications protocol used is the CAN (Controller Area Network) 
Peripheral Interface (CPI) protocol. 
CPI is a proprietary interface for communications between Campbell Scientific 
dataloggers and Campbell Scientific CDM peripheral devices. It consists of a 
physical layer definition and a data protocol. CDM devices are similar to 
Campbell Scientific SDM devices in concept, but the use of the CPI bus 
enables higher data-throughput rates and use of longer cables. CDM devices 
require more power to operate in general than do SDM devices. 
C.1 CDM Interconnection and Datalogger Connection
C.1.1 Power
The transmission of dc power to CDM modules is not governed by the CPI 
specification but is left to the system integrator to implement. Most CDMs 
require modest power from a regulated dc voltage between 11 and 32 Vdc. 
This power may come from the datalogger power source or through the 
datalogger wiring panel. 
C.1.2 Interconnect Cable
Current Campbell Scientific dataloggers require the SC-CPI Interface to 
connect with one or more CDM devices. Cat5e cable with RJ45 terminations 
connects a CDM devices with the SC-CPI and other CDM devices. Cabling 
and connections must be managed carefully to achieve the highest data rates 
and longest transmission distances. Ideally, four twisted-pair (data, 
synchronization, clock, and ground) are contained in a single shielded cable. 
The data pair carries data between the SC-CPI and CDM using the CAN 
protocol with ISO 11898 as the electrical standard. The CAN protocol covers 
device addressing, bus arbitration, prioritization, bit-error checking, and failed-
message retransmission. The synchronization pair uses the RS-485 (TIA/EIA-
485A) electrical standard. This signal is a pulse that marks the beginning of 
each scan. CDMs use this precision timing to remain synchronized, to latch, 
and to buffer and transmit data to the datalogger unprompted over the data pair. 
Use a pn 28558 termination resistor plug (included with the pn 29370 CPI 
network kit) on the final device of a CPI chain to ensure cable communications 
are working at high speeds and over very long distances. CPI pin assignments 
are provided in the following figure as implemented with Cat5e cabling. 
C-1