ANALOG INPUT CONVERSION FACTOR
The following table describes how real-world inputs are scaled into the controller. Given a known input
current, the data value is configured by using the conversion factor from the table. The following formula
is used: Data = Input Current (mA) / Conversion Factor
Example: The user selects a current range of 0 to +20mA:
1) The known input current is 14mA.
2) Using the table, the conversion factor for the current range of 0 to +20mA is .000625.
3) To determine the data value, the formula is used:
Data = Input Current (mA) / Conversion Factor
22400 = 14mA / 0.000625
Conversion of Real-World Inputs into Controller
Selected Current
Range
Input Current (mA)
Data
Conversion Factor
+20.47 32752
+20.00 32000
0 to +20mA
0 0
0.000625
6
ANALOG CONVERSION OUTPUT FACTOR
The following table describes how program data values are scaled to real-world analog voltage outputs by
the module. Given a desired output current, the data value is converted by using the conversion factor
from the table. The following formula is used: Data = Output Current (mA) / Conversion Factor
Example: The user selects a current range of +20mA:
1) The desired output current is 12mA.
2) Using the table, the conversion factor for the current range of +20 mA is 0.000625.
3) To determine the data value, the formula is used:
Data = Output Current (mA) / Conversion Factor
19200 = 12mA / 0.000625
Conversion of Real-World Outputs into Controller
Selected Current
Range
Output Current (mA)
Data
Conversion Factor
+20.47 32752
+20.00 32000
0 to +20mA
0 0
0.000625