4 configuration – Horner APG SmartStack I/O HE-MIX902* User Manual
Page 4

PAGE 4
10 NOV 2006
MAN0292-08
MIX902
This Data Sheet is published individually & also as a part of the SmartStack Supplement (SUP0246-05).
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
Specification for transient voltage suppressors (transorbs) used on output circuitry is 33V, 300W.
4 CONFIGURATION
Note: The status of the I/O can be monitored in Cscape Software.
Preliminary configuration procedures that apply to SmartStack
™ Modules are contained in the hardware
manual of the controller you are using. Refer to the Additional References section in this data sheet for
a listing of hardware manuals.
Module Setup Tab
The Module Setup is used in applications where it is necessary to change the default states or values of
the outputs when the controller (e.g., OCS100) enters idle/stop mode.
1. For Digital Outputs: The default turns the outputs OFF when the controller enters idle/stop mode. By
selecting the Module Setup tab, each output can be set to either turn ON, turn OFF or to hold the last
state. Generally, most applications use the default settings.
Warning: The default turns the digital outputs OFF when the controller enters idle/stop mode.
To avoid injury of personnel or damages to equipment, exercise extreme caution when
changing the default settings.
VCC
To
Controller
I/O Connector
iI1
C
SmartStack Digital Input
Field
Side
From
Controller
V+
Q
VC
I/O Connector
Field
Side
SmartStack Digital Output